Electrical installation – Banner SI-HG63 Hinge Style Switches User Manual

Page 7

Advertising
background image

Figure 14. Align to "B"

7. Press the switch element into the enclosure again until it reaches the internal stop.
8. Install a new red plastic washer (from the accessories bag included with the switch) onto the switch cylinder.

Figure 15. Install a new plastic washer

9. If the hinge position on the switch is being changed (changing from a left hinge to a right, for example), remove the rectangular plug

from the switch housing and attach the hinge to that side. Install the hinge onto the switch and rotate 30° to seat. Fasten the switch
to the hinge using the supplied tool and the screws removed in step 1. The countersunk screw max. torque is 2 Nm.

Figure 16. Change the hinge position

10. Set the new switch point setting as required.

Electrical Installation

WARNING: Shock Hazard and Hazardous Energy
Always disconnect power from the safety system (for example, device, module, interfacing, etc.) and
the machine being controlled before making any connections or replacing any component.
Electrical installation and wiring must be made by Qualified Personnel and must comply with the relevant
electrical standards and wiring codes, such as the NEC (National Electrical Code), ANSI NFPA79, or IEC
60204-1, and all applicable local standards and codes.
Lockout/tagout procedures may be required. Refer to OSHA 29CFR1910.147, ANSI Z244-1, ISO 14118,
or the appropriate standard for controlling hazardous energy.

A Qualified Person possesses a recognized degree or certificate or has extensive knowledge, training, and experience to solve problems
relating to the emergency stop installation.

Hinge Wing Safety Interlock Switches

Datasheet
129465_web Rev.
D

www.bannerengineering.com - tel: 763-544-3164

7

Advertising