Fault Exclusion

An important concept within the category requirements of ISO 13849-1 is the probability of the occurrence of the failure, which can be
decreased using the "fault exclusion" method. This method assumes that the possibility of certain well-defined failure(s) can be reduced
to a point where the resulting fault(s) can be disregarded.
Fault exclusion is a tool a designer can use during the development of the safety-related part of the control system and the risk assess-
ment process. It allows the designer to eliminate the possibility of various failures and justify it through the risk assessment process to
meet the requirements of Categories 2, 3 or 4. See ISO 13849-1/-2 for further information.

Monitoring of Safety Devices

Requirements vary widely for the level of control reliability or safety category per ISO 13849-1 (EN954-1) in safety applications. While
Banner Engineering always recommends the highest level of safety in any application, it is the responsibility of the user to safely install,
operate and maintain each safety system and comply with all relevant laws and regulations.
Although only two applications are listed, the Module can monitor a variety of devices as long as the input requirements are complied with
(see Electrical Installation and Specifications). The Safety Module does not have 500 ms simultaneity between inputs and thus cannot be
used for monitoring a two-hand control. In all cases, the safety performance (integrity) must reduce the risk from identified hazards as
determined by the machine's risk assessment .

WARNING: Emergency Stop Functions
Do not mute or bypass any Emergency Stop device.
ANSI B11.19, ANSI NFPA79 and IEC/EN
60204-1 require that the Emergency Stop function remain active at all times.

Emergency Stop Push Buttons and Rope/Cable Pull Switches

The safety inputs can be interfaced with positive-opening switches to monitor an emergency-stop (E-stop) push button or rope/cable pull.
The switch must provide one or two contacts for safety which are closed when the switch is armed. Once activated, the E-stop switch
must open all its safety-rated contacts, and must require a deliberate action (such as twisting, pulling, or unlocking) to return to the
closed-contact, armed position. The switch must be a "positive-opening" (or direct-opening) type, as described by IEC 60947-5-1.
Standards ANSI NFPA 79, IEC/EN 60204-1, and ISO 13850 specify additional emergency stop switch device requirements, including the
following:

• Emergency-stop push buttons shall be located at each operator control station and at other operating stations where emergency

shutdown is required.

• Stop and emergency-stop push buttons shall be continuously operable and readily accessible from all control and operating stations

where located. Do not mute or bypass E-stop buttons or rope/cable pulls.

• Actuators of emergency-stop devices shall be colored red. The background immediately around the device actuator shall be colored

yellow (where possible). The actuator of a push-button-operated device shall be of the palm or mushroom-head type.

• The emergency-stop actuator shall be a self-latching type.

For Rope/Cable Pull Installations Only:

• The wire rope should be easily accessible and visible along its entire length. Markers or flags may be fixed on the rope to increase its

visibility.

• Mounting points, including support points, must be rigid.
• The rope should be free of friction at all supports. Pulleys are recommended.

Some applications may have additional requirements; comply with all relevant regulations. See the device manufacturer installation in-
structions for complete information (such as ES-..A-5A p/n 122365, SSA-EB..-.. p/n 111880, or RP-RM83F.. p/n 141245 data sheets).

WARNING: Emergency Stop Functions
Do not mute or bypass any Emergency Stop device.
ANSI B11.19, ANSI NFPA79 and IEC/EN
60204-1 require that the Emergency Stop function remain active at all times.

Interlocked Guards (Gates)

The safety inputs can be interfaced with positive-opening safety switches to monitor the position of an interlock guard or gate. Each
switch must provide electrically isolated contacts: at minimum, one normally closed (N.C.) contact from each individually mounted switch.

ES-FA-9AA and ES-FA-11AA E-Stop Safety Modules

P/N 060606 Rev. F

www.bannerengineering.com - tel: 763-544-3164