Status codes – Bryant Evolutiont Series s with Puronr Refrigerant 286A User Manual

Page 14

Advertising
background image

14

Status Codes

Table 6 shows the status codes flashed by the amber status light.
Most system problems can be diagnosed by reading the status code

as flashed by the amber status light on the control board.
The codes are flashed by a series of short and long flashes of the

status light. The short flashes indicate the first digit in the status

code, followed by long flashes indicating the second digit of the
error code.

The short flash is 0.25 seconds ON and the long flash is 1.0 second
ON. Time between flashes is 0.25 seconds. Time between short

flash and first long flash is 1.0 second. Time between code
repeating is 2.5 seconds with LED OFF.
EXAMPLE:
3 short flashes followed by 2 long flashes indicates a 32 code.
Table 6 shows this to be low pressure switch open.

Table 6 – TROUBLESHOOTING

OPERATION

FAULT

AMBER LED

FLASH

CODE

POSSIBLE CAUSE AND ACTION

Standby – no call for unit operation

None

On solid, no

flash

Normal operation

Low Stage Cool/Heat Operation

None

1, pause

Normal operation

High Stage Cool/Heat Operation

None

2, pause

Normal operation

System Commu-

nications Failure

16

Communication with User Interface lost. Check wiring to UI, indoor and

outdoor units

Invalid Model Plug

25

Control does not detect a model plug or detects an invalid model plug. Unit

will not operate without correct model plug.

High Pressure

Switch Open

31*

High---pressure switch trip. Check refrigerant charge, outdoor fan operation

and coils for airflow restrictions.

Low Pressure

Switch Open

32*

Low---pressure switch trip. Check refrigerant charge and indoor air flow.

Control Fault

45

Outdoor unit control board has failed. Control board needs to be replaced.

Brown Out (230 v)

46

Line voltage < 187v for at least 4 seconds. Compressor and fan operation

not allowed until voltage>190v. Verify line voltage.

No 230v at Unit

47

There is no 230v at the contactor when indoor unit is powered and cooling/

heating demand exists. Verify the disconnect is closed and 230v wiring is

connected to the unit.

Outdoor Air Temp

Sensor Fault

53

Outdoor air sensor not reading or out of range. Ohm out sensor and check

wiring.

Outdoor Coil

Sensor Fault

55

Coil sensor not reading or out of range. Ohm out sensor and check wiring.

Thermistors out of

range

56

Improper relationship between coil sensor and outdoor air sensor. Ohm out

sensors and check wiring.

Low Stage

Thermal Cutout

71*

Compressor operation detected then disappears while low stage demand

exists. Possible causes are internal compressor overload trip or start relay

and capacitor held in circuit too long (if installed).

High Stage

Thermal Cutout

72*

Compressor operation detected then disappears while high stage demand

exists. Possible causes are internal compressor overload trip or start relay

and capacitor held in circuit too long (if installed).

Contactor Shorted

73

Compressor voltage sensed when no demand for compressor operation

exists. Contactor may be stuck closed or there is a wiring error.

No 230V at

Compressor (288A

Only)

74

Compressor voltage not sensed when compressor should be starting. Con-

tactor may be stuck open or there is a wiring error.

Low Stage Did Not

Start

(286A Only)

75

Specified start voltage at VR terminal was not achieved in low stage. Start

relay was de---energized after 1 second.

Low Stage Did Not

Start 3 times (286A

Only)

76

For 3 consecutive low stage starts, the specified start voltage at VR terminal

was not achieved & start relay was de---energized. Low stage locked out for

30 minutes.

High Stage Did Not

Start

(286A Only)

77

Specified start voltage at VS terminal was not achieved in high stage. Start

relay was de---energized after 1 second.

High Stage Did Not

Start 3 times (286A

Only)

78

For 3 consecutive high stage starts, the specified start voltage at VS terminal

was not achieved & start relay was de---energized. High stage locked out for

30 minutes.

Low Stage

Thermal Lockout

81

Thermal cutout occurs in three consecutive low/high stage cycles. Low

stage locked out for 4 hours or until 24v power recycled.

High Stage

Thermal Lockout

82

Thermal cutout occurs in three consecutive high/low stage cycles. High

stage locked out for 4 hours or until 24v power recycled.

Low---Pressure

Lockout

83

Low pressure switch trip has occurred during 3 consecutive cycles. Unit

operation locked out for 4 hours or until 24v power recycled.

High---Pressure

Lockout

84

High pressure switch trip has occurred during 3 consecutive cycles. Unit

operation locked out for 4 hours or until 24v power recycled.

Low Contactor

Open

(286A Only)

85

Compressor voltage not sensed when compressor should be starting. Low

stage contactor may be stuck open or there is a wiring error.

High Contactor

Open

(286A Only)

87

Compressor voltage not sensed when compressor should be starting. High

stage contactor may be stuck open or there is a wiring error.

*

Sequence: Compressor contactor is de---energized and outdoor fan is energized for up to 15 minutes. If demand still exists, control will energize compressor

contactor after 15 minute delay. If fault is cleared, unit will resume operation. If fault still exists, fan shuts off, and error code continues to flash. Control will

attempt re---start every 15 minutes. Cycling low voltage defeats the 15 minute delay.

286A

/288A

Advertising