Warning – Bryant Evolutiont Series s with Puronr Refrigerant 286A User Manual

Page 6

Advertising
background image

6

NOTE: Install branch circuit disconnect of adequate size per NEC
to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440--14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires

from disconnect through power wiring hole provided and into unit
control box.

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault

should occur. The ground may consist of electrical wire or

metal conduit when installed in accordance with existing

electrical codes.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 5.

DISCONNECT

PER N. E. C. AND/OR

LOCAL CODES

CONTACTOR

GROUND

LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

A91056

Fig. 5 -- Line Power Connections

Connect Control Wiring

Route low voltage control wires through control wiring grommet
and connect leads to control board.
For Evolution, connect to ABCD only.

For standard

non--communicating thermostats, connect to standard thermostat

connections R, C, W, Y1, Y2, and O.

General Information

Use No. 18 AWG color--coded, insulated (35°C minimum) wire for
all installations.
All wiring must be NEC Class 1 and must be separated from

incoming power leads.
Use furnace transformer, fan coil transformer, or accessory

transformer for control power, 24v/40va minimum. The outdoor
unit requires a minimum of 27va/24vac control power.

Final Wiring Check

IMPORTANT: Check factory wiring and field wire connections
to ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

Furnish power to crankcase heater a minimum of 24 hr before

starting unit. To furnish power to heater only, set thermostat to
OFF and close electrical disconnect to outdoor unit.
NOTE: On 286A models, starting the compressor without a
minimum of 12 hours of crankcase heat prior to initial start--up
may result in a compressor chattering noise and possible damage to
the compressor.

Install Accessories

Refer to the individual instructions packaged with kits or
accessories when installing.

Make Airflow Selections

Airflow Setup for Evolution Control Furnace of FE

Fan coil (communicating)
When using an Evolution User Interface, airflow is

automatically selected based on equipment size. See User

Interface

Installation

Instructions

for

available

adjustments.
Airflow Selection for Variable Speed Furnaces for

Non--Communicating (non--Evolution) Thermostats

The variable speed furnaces provide blower operation to match the

capacities of the compressor during high and low stage cooling

operation, The furnace control board allows the installing
technician to select the proper airflows for each stage of cooling.

Below is a summary of required adjustments. See furnace
installation instructions for more details:

1. Turn SW1--5 ON for 400 CFM/ton airflow or OFF for 350

CFM/ton airflow. Factory default is OFF.

2. The A/C DIP switch setting determines airflow during high

stage cooling operation. Select the A/C DIP switch setting

corresponding to the available airflow shown in the furnace
installation instructions that most closely matches the re-
quired airflow shown in the air conditioning Product Data

for HIGH speed.

3. The CF DIP switch setting determines airflow during low

stage cooling operation. Select the CF DIP switch setting
corresponding to the available airflow shown in the furnace

installation instructions that most closely matches the re-
quired airflow shown in the air conditioning Product Data
for LOW speed.

If a higher or lower Continuous Fan speed is desired, the
Continuous Fan speed can be changed using the fan switch on the

thermostat. Refer to the furnace installation instructions for details

of how to use this feature.

Airflow Selection for FV4 Fan Coils for Non--Commu-

nicating (Non--Evolution) Thermostats

The FV4B provides high-- and low--stage blower operation to

match the capacities of 286A compressor at high-- and low--stage.

The FV4C provides high-- and low--stage blower operation to

match the capacities of 288A compressor at high-- and low--stage

(units containing circuit board HK38EA015 or newer). To select
recommended airflow, refer to FV4 Installation Instructions. The

FV4 utilizes an Easy Select control board that allows the installing

technician to select proper airflows. For adjustments to control
board, select appropriate HP SIZE and CFM ADJUST setting. This

fan coil has an adjustable blower off delay factory set at 90 sec for
high-- and low--stage blower operation.

286A

/288A

Advertising