I/O

Poin

t

Modbus Holding Register

I/O Type

Units I/O Range

Holding Register
Representation

Terminal

Block La-

bels

Gateway

or DX85

Any Node

Min. Val-
ue

Max.
Value

Min.
(Dec.)

Max.
(Dec.)

6

6

6 + (Node# × 16)

7

7

7 + (Node# × 16)

Reserved

8

8

8 + (Node# × 16)

Device Message

9

9

9 + (Node# × 16)

Discrete OUT 1

-

0

1

0

1

DO1

10

10

10 + (Node# × 16)

Discrete OUT 2

-

0

1

0

1

DO2

11

11

11 + (Node# × 16)

Discrete OUT 3

-

0

1

0

1

DO3

12

12

12 + (Node# × 16)

Discrete OUT 4

-

0

1

0

1

DO4

13

13

13 + (Node# × 16)

14

14

14 + (Node# × 16)

15

15

15 + (Node# × 16)

Control Message

16

16

16 + (Node# × 16)

Reserved

The lower eight bits of the 16-bit unsigned register represent each of the eight digital inputs. Therefore, if all inputs are OFF (0) the
register contains 0x0000; if all inputs are ON (1) the register contains 0x00FF (255).
When your wireless network does not include a host system, the eight input/four output Node must be mapped to the four input/eight
output Gateway.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Inpu t 8

Inpu t 1

Inpu t 2

Device Configuration

Setting the Slave ID on a DX85 Remote I/O Device

On a DX85 Modbus RTU Remote I/O device, use the rotary dials to set the device’s Slave ID.

In Rotary Dial Decimal Mode, the left dial acts as the left digit and the right dial acts as the right
digit, allowing the Slave ID to be set from 01 through 99.
In Rotary Dial Hex Mode, the left dial acts as the left digit and the right dial acts as the right digit,
allowing the Slave ID to be set from 01 through F7 for a total of 247 slaves.
The 12 I/O DX85 models use Rotary Dial Decimal Mode and do not have a DIP switch selection
for this option.
To configure the DX85 using the UCT, the DX85's Slave ID must be set to 01.

SureCross DX85 Modbus RTU Remote I/O Device

P/N 134324 rev. F

www.bannerengineering.com - tel: 763-544-3164

5