Banner SureCross DX85 Modbus RTU Remote I/O Device User Manual

Page 6

Advertising
background image

DIP Switch Changes

Before making any changes to the DIP switch positions, disconnect
the power. For devices with batteries integrated into the housing,
remove the battery for at least one minute.
DIP switch changes will not be recognized if power isn't cycled to
the device.

Accessing the DIP Switches

To access the DIP switches, follow these steps:

1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the bottom housing. For integrated battery models (no ribbon cable) and

Class I, Division 2 certified devices (ribbon cable is glued down), skip this step.

4. Remove the black cover plate from the bottom of the device's cover.

The DIP switches are located behind the rotary dials. After making the neces-
sary changes to the DIP switches, place the black cover plate back into posi-
tion and gently push into place. Plug the ribbon cable in after verifying that
the blocked hole lines up with the missing pin. Mount the cover back onto the
housing.

DIP Switch Settings for a DX85

Use the DIP switches 1 through 4 on the board to set the baud rate and parity and DIP switch 5 to set the rotary dial mode.

DIP Switches

1

2

3

4

5

Baud Rate: 19200

OFF*

OFF*

Baud Rate: 38400

OFF

ON

Baud Rate: 9600

ON

OFF

Baud Rate: 19200

ON

ON

Parity: None

OFF*

OFF*

Parity: Even

OFF

ON

Parity: Odd

ON

OFF

Parity: None

ON

ON

Rotary Dial Decimal Mode

OFF*

Rotary Dial Hex Mode

ON

* Default configuration

SureCross DX85 Modbus RTU Remote I/O Device

6

www.bannerengineering.com - tel: 763-544-3164

P/N 134324 rev. F