Units Description

Definition

LCD: 0000.0F

10

Asynchronous
Counter, 32-bit

The 32-bit counter value records counts up to 4.29 billion.

LCD: 0000 0000

11

Asynchronous
Counter, 16-bit

The 16-bit counter value records counts up to 65535.

LCD: 0000

Output Units

Units Description

Definition

0

Raw

Displays the raw A/D conversion data with data ranges from 0 to 65535. This units type is typically used
only for factory calibration.

LCD: Raw A/D hex value

1

4 to 20 mA

Analog unit. Modbus register contents are scaled such that 0 represents 4 mA and 65535 represents 20
mA.

LCD: 4.00mA–20.00mA

2

0 to 20 mA

Default analog input unit. Modbus register contents are scaled such that 0 represents 0 mA and 65535
represents 20 mA.

LCD: 0.00mA–20.00mA

3

Discrete (ON/
OFF)

Default discrete unit.

LCD: ON/OFF

4

0 to 10V (Volts) Analog unit using 0 to 10V instead of current. Modbus register contents are scaled such that 0 represents

0V and 65535 represents 10V.

LCD: 0.00V–10.00V

5

Signed Analog,
0 to 10V

For a signed value, such as temperature, that is to be converted to a voltage out value. Use null to set the
start point and span to define the range. The null value is the starting temperature to be associated with
0V. The span is the entire temperature range that is to be associated with 0 to 10V.

LCD: 0.00V–10.00V

6

Signed Analog,
0 to 20 mA

For a signed value, such as temperature, that is to be converted to a mA out value. Use null to set the start
point and span to define the range. The null value is the starting temperature to be associated with 0 mA.
The span is the entire temperature range that is to be associated with 0 to 20 mA.

LCD: 0.00mA–20.00mA

7

Unsigned Ana-
log, 0 to 20 mA

For unsigned values, such as a counter, that is to be converted to a mA out value. Use the null to set the
start point and span to define the range. The null value is the distance to be associated with 0 mA. The
span is the entire distance range that is to be associated with 0 to 20 mA.

LCD: 0.00mA–20.00mA

8

Signed Analog,
4 to 20 mA (A)

In older models, this units type is for degree Celsius conversions only. Use null to set the start point and
span to define the range. The null value is the starting temperature to be associated with 4 mA. The span
is the entire temperature range that is to be associated with 4 to 20 mA. For newer firmware models, type
codes 8 and 9 are treated the same.

LCD: 4.00mA–20.00mA

SureCross User Configuration Tool (UCT)

Rev. G

www.bannerengineering.com - tel: 763-544-3164

27