Output Scale

Fullscale (range)

Offset

0 to 10V

10V

0V

Fullscale. Defined in the table; the output range.

Span. The total range of values mapped to the output.

Null. The starting point for the output scale.

Input Value. The value mapped to the output.

Offset. Defined in the table; the starting output value.

Example: Temperature Map

Map a temperature input from a Node to a 4–20 mA output. The starting temperature is −20°F and the last temperature will be 50°F (4
mA = −20°F, 20 mA = 50°F). This defines the null as −20°F and the span as 70.

With an input temperature value of −5°F, the output value will be:

Output = (Fullscale ÷ Span)(InValue − Null) + Offset

(Fullscale ÷ Span) = 16 ÷ 70 = 0.22857

(Value − Null ) = −5 − (−20) = 15

Offset = 4

Output = 0.22857 × 15 + 4 = 7.42 mA

Example: Distance Map

Map a distance input from a Node to a 0–10V output. The starting distance is 200mm and the last distance will be 2000mm (4 mA =
200mm, 20 mA = 2000mm). This defines the null as 200 and the span as 1800.

With an input distance reading of 1560mm, the output value will be:

Output = (Fullscale ÷ Span)(InValue − Null) + Offset

(Fullscale ÷ Span) = 10 ÷ 1800 = 0.00555

(Value − Null ) = 1560 − 200 = 1360

Offset = 0

Output = 0.00555 × 1360 + 0 = 7.54V

Alarm Conditions

The standard alarm conditions are as follows:

Unsigned Alarm = 0xFFFF

Signed Alarm = 0x7FFF

If special alarm conditions are needed, consult the factory for details.