Bryant Air Coold Split System 575B User Manual

Page 10

Advertising
background image

10

Duplex 575C120, 541A180 with 524A-H240 or 524A-H300

In order to properly connect two heat pump condensing
units to a single 524A-H packaged air handler, it is
necessary to add field-supplied Fan Coil Relay Board(s),
P/N 33ZCRLYBRD. Relay board(s) no. 1 and no. 2 should be
installed in the control box of condensing unit.

IMPORTANT: The common (COM) terminals from the fan
coil relay board(s) must be connected to the ‘C’ terminal in
condensing unit ‘A’.

Route thermostat cable or equivalent single leads of
no. 18 AWG (American wire Gage) colored wire from subbase
terminals through conduit in unit to low-voltage connections
as shown on unit wiring diagram and Fig. 12 and 13.

NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated wire
(35 C minimum). For 51 to 75 ft, use no. 16 AWG insulated
wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated
wire (35 C minimum). All wire larger than no. 18 AWG cannot
be directly connected to the thermostat and will require a junc-
tion box and a splice at the thermostat.

Table 7 — Electrical Data

LEGEND

*Units are suitable for use on electrical systems where voltage supplied

to the unit terminals is not below or above the listed limits.

NOTES:

1. The MCA and MOCP values are calculated in accordance with the

NEC, Article 440.

2. Motor RLA and LRA values are established in accordance with

Underwriters’ Laboratories (UL), Standard 1995.

3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option

or a field-installed accessory and is 115-v, 1 ph, 60 Hz.

UNIT

FACTORY-

INSTALLED

OPTION

NOMINAL VOLTAGE

(V-Ph-Hz)

VOLTAGE RANGE*

COMPRESSOR

FAN MOTORS

POWER SUPPLY

Min

Max

RLA

LRA

FLA

MCA

MOCP

575B

072

NONE

208/230-3-60

187

253

18.9

146

5.1

28.7

45

460-3-60

414

506

9.5

73

2.6

14.5

20

575-3-60

517

633

7.6

58

1.2

10.7

15

575C

090

NONE OR DISCONNECT

208/230-3-60

187

254

29.0

190

1.5

39.0

60

CONVENIENCE OUTLET

43.8

60

NONE OR DISCONNECT

460-3-60

418

506

15.0

95

0.7

19.8

30

CONVENIENCE OUTLET

21.9

30

120

NONE OR DISCONNECT

208/230-3-60

187

254

34.0

225

1.5

45.0

60

CONVENIENCE OUTLET

50.0

70

NONE OR DISCONNECT

460-3-60

418

506

17.0

114

0.7

23.0

30

CONVENIENCE OUTLET

25.0

30

NONE OR DISCONNECT

575-3-60

523

632

14.0

80

0.7

18.0

25

CONVENIENCE OUTLET

20.0

25

541A

180

NONE

208/230-3-60

187

253

63.6

266

4.3

87.5

125

460-3-60

414

528

29.3

120

2.3

40.7

60

575-3-60

518

660

23.8

96

1.8

33.0

50

FLA

Full Load Amps

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

RLA

Rated Load Amps

Fig. 8 — Wiring Diagram — 575C090,120 —

Control Transformer