Bryant Air Coold Split System 575B User Manual

Page 6

Advertising
background image

6

Table 1 — Physical Data — 575B072, 575C090,120 and 541A180 Units

*Unit is factory supplied with holding charge only.

†Typical operating charge with 25 ft of interconnecting pipe.

**Storage capacity of condenser coil with 80% full of liquid at 95 F.

UNIT

575B072

575C090

575C120

541A180

NOMINAL CAPACITY (tons)

6

7.5

10

15

OPERATING WEIGHTS (lb)

Aluminum-Fin Coils (standard)

345

464

506

803

Copper-Fin Coils (optional)

N/A

565

607

945

REFRIGERANT*

R-22

Operating Charge, Typical (lb)†

20

20

22

37

Shipping Charge (lb)

1

2

2

3

COMPRESSOR

Scroll

Semi-hermetic reciprocating

Qty...Model

1...SR_75

1...SR_94

1...ZR125

1...06DF537

Oil Charge (oz)

88

90

110

128

No. Cylinders

N/A

6

Speed (rpm)

3500

1750

OUTDOOR FANS

Qty...Rpm

1…1100

2…1100

2…1075

Diameter (in.)

26

22

26

Nominal Hp

3

/

4

1

/

4

1

/

2

Nominal Airflow (cfm total)

6500

11,000

Watts (total)

750

570

1460

OUTDOOR COILS (Qty)

1

2

1

Face Area (sq ft total)

24

29.2

29.2

Rows...Fins/in.

2…18

2…17

3…15

Storage Capacity (lb)**

17.3

34.2

40.1

CONTROLS
Pressurestat Settings (psig)

High Pressure

Open

420

428 ± 10

395 ± 20

Close

300

320 ± 20

295 ± 20

Low Pressure

Open

5

7 ± 3

7 ± 3

Close

20

22 ± 5

22 ± 5

DISCHARGE GAS THERMOSTAT

Cutout (°F)

N/A

270 ± 9

N/A

Cut in (°F)

N/A

190 ± 13

N/A

PIPING CONNECTIONS (in. ODM)

Vapor

1

1

/

8

1

1

/

8

1

3

/

8

1

5

/

8

Liquid

5

/

8

1

/

2

1

/

2

5

/

8

Advertising