PRIMARY OPERATIONAL GUIDE

BECKETT GENISYS 7505

Sequence of Operation

MIS-2491

BECKETT GENISYS

MODEL 7505

BURNER STATES

1. Standby: The burner is idle, waiting for a call

for heat.

2. Valve-On Delay (Prepurge): The igniter and

motor are on while the control delays turning on
the oil solenoid valve for the programmed time.

3. Trial for Ignition: The fuel valve is opened. A

flame should be established within the factory
set trial for ignition time (“lockout time”).

4. Lockout: The control has shut the burner down

for one of the following safety reasons:

The trial for ignition (lockout) time expires
without flame being established.

The cad cell detects flame during Valve-On
Delay.

The Recycle mode 30-second time budget
expires (see “Recycle” section for complete
explanation of recycle time budget).

If the control locks out three times without
completing a successful call for heat, the control
enters Restricted (Hard) Lockout, and must be reset
by a technician. Hold the reset button for 15
seconds until the red light shuts off to reset from
Restricted Lockout.

5. Ignition Carryover: Once flame is established,

the igniter remains on for 10 additional seconds
to ensure flame stability.

6. Run: The flame is sustained until the call for

heat is satisfied. The burner is then sent to
Motor-Off Delay (Postpurge), if applicable, or it
is shut down and sent to Standby.

7. Recycle: If the flame is lost while the burner is

firing, the control shuts down the burner, enters
a 60-second recycle delay and then repeats the
ignition sequence. The control will continue to
Recycle each time the flame is lost until the
accumulated oil-flow-without-flame time
reaches 30 seconds, at which point the control
will go into lockout. This feature prevents
excessive accumulation of oil in the appliance
firing chamber.

8. Motor-Off Delay: If applicable, the fuel valve is

closed and the control delays turning the motor
off for the set motor-off delay time before the
control returns to standby.

9. Pump Prime: The igniter and motor are on with

the oil valve open for up to 4 minutes. During
Pump Prime mode, the cad cell is disregarded,
allowing the technician to prime the pump
without having to jumper the cad cell.

RESET BUTTON OPERATION

Table A explains what action the control
will take when the reset button is pressed for
different lengths of time during the various
burner operating states.