HS-3100/3200 Operator’s Manual

7

The Main Menu has the following selections:

Status: Displays the current status of various parts of the panel. The following options are
available:

More: Displays the next screen of menu options. When the last screen of the menu is
displayed the next screen will be the first one again.

Misc. Trouble: Displays any troubles with the bells, releasers, AC power, batteries, etc.,
that are not shown elsewhere. Only sections in trouble will be displayed. Press <Enter>
to go to the next screen. See section 2.2 for a list of all possible messages.

Alarm List: Displays the Alarm List under manual control. See Alarm List above, Using
the Keypad.

Addressable: This menu has the following options:

Select: Displays the current status of a single device. The device address is entered
into the screen saying "circuit or circuit.device". If only a circuit number is entered, the
first programmed device on that circuit will be displayed. If <Enter> is pressed
without any entry, the first addressable device will be displayed. <Clear> will remove
any values entered. If there is no value entered, <Clear> will return to the Status
Menu. If the selected device is not in the database, the next device in the database is
shown.

The display shows the device address in the top left corner and the current condition
codes in the top right corner (see section 2.0 for a description of the condition codes).
The second line shows the headings for the third line, which contains the analog
values sent from the device. Press <Enter> to view the next device or <Clear> to
get the address input screen.

Print Sensors: Prints the analog value for every addressable smoke and thermal
detector. This is the value of the detector at the time the command is issued.

Identification: Displays a sequence of screens that provide the program and version, the
panel's serial number, database version, etc. Press <Enter> to go to the next screen.

Print Database: This function is restricted to Level 1. Print the current configuration
(values entered through the LCD menu) and downloaded database of the panel to screen
14 of the service terminal.

Print Archive: This function is restricted to Level 1. Prints all or part of the history. A
selection menu is presented to select which kinds of events to print. The choices are: All,
Alarms, Supervisory, Trouble, Monitor, Bypass and Non-reporting.

Each entry consists of one or two lines. The information provided on the first line, from the
left, is:

1. Event Number
2. Time (24 Hour Clock)
3. Date (MM/DD/YY Format)
4. Condition Code and Zone Number (see section 2.1)
5. Description

A second line will be printed for addressable devices if a message exists in the database.

This history is sent to the service terminal port if Screen 14 is active. Screen 14 of the
service terminal is a copy of all items sent to the printer port.

Archive: The archive is a list of the last 1000 events (approx.). These include all signals,
programming changes, time/date changes, etc., that have occurred. Test signals may or may not
be recorded but "Test On" and "Test Off" are. The archive is not lost when there is a loss of both
AC and battery power. Each entry includes a short description of the event, and the date and time