HS-3100/3200 Operator’s Manual

4

System
Reset

System Reset resets part or all of the system.

The rightmost green LED flashes when the system, or part of the system,
can be reset.

The leftmost green LED flashes if the ground fault relay is activated.

Press System Reset to deactivate the ground fault relay to check for restores
and additional ground faults. If ground faults remain, the relay will be re-
activated after 5 to 30 seconds.

Pressing System Reset with no LEDs flashing will operate any relays that are
not used by the system and deactivate any Aux Power outputs. The time they
remain open is determined by the Duration time programmed. If the Duration is
0, the relay or Aux Power output will not operate.

Notes:
1.

The system cannot be reset until all circuits and devices are reset.

2.

If both LEDs are flashing, the rightmost LED function has precedence.

3.

The green LED will remain flashing after System Reset is pressed until

addressable devices have had their LEDs reset.

Relay
Disconnect

Causes the local function relays and control modules to ignore any new alarms.
Press again to restore normal operation. The yellow LED will flash while active.
If no relays nor control modules can be disconnected, Relay Disconnect will do
nothing. This function can be set to Privilege Level 0 or 1.

Test Mode

Places the panel into test mode. Press again to return to normal mode. The
yellow LED will flash while in test mode. This function can be set to Privilege
Level 0 or 1. It follows the Disconnect privilege level (set in MHI). During test
mode, the panel annunciator becomes non-latching for the zone(s) under test.
The common indicators, bells, relays are not activated, and no signal is sent out
of Port 3. Test signals can be archived or not as required.

Before beginning testing, the circuits/devices to be tested must be selected. All
unselected circuits/devices will operate normally. Be sure that the panel is in
test mode. To select circuits/devices, select PROGRAM from the Main Menu on
the LCD. The arrow keys move the cursor and the <Enter> key selects the item.
Then select ADDRESSABLE. Then select TEST. For addressable devices,
enter the device circuit and address for each device to be tested. <Clear> will
return to the previous menu.

When test mode is ended, all devices selected for testing automatically return
to normal operation.

Note: There is no Ground Fault isolation while Test Mode is active.

Signal
Disconnect

Disables sounding of the bells. The buzzer beeps every 2 seconds while the
bells are disabled. This beeping is suppressed while a privileged level is
entered in the panel. Press Signal Disconnect again to re-enable the bells. The
yellow LED will flash while the bells are disabled. Signal Disconnect is not
available if the bells are already activated. This function can be set to Privilege
Level 0 or 1.