Harrington Signal WHS User Manual

Page 2

Advertising
background image

24VDC CLEAR Lens Indoor Strobe Current Ratings

GEC24 and

GES24 Series

Available Candela

GEC3-24 and

GES3-24 Series

Available Candela

Strobe

Candela

Regulated 24VDC

Max. Operating

Current(mA)

Regulated 24VFWR

Max. Operating

Current (mA)

1

15

42

77

15/75

67

113

30

58

102

60

97

161

75

116

225

110

161

256

177

213

341

WGEC24, WGES24, WGECA24, WGESA24, WGECB24, WGESB24, WGECG24, WGESG24, WGECR24, WGESR24 PRODUCT INFORMATION

Models

Color Lens

WGECA24, WGESA24

Amber

WGECB24, WGESB24

Blue

WGECG24, WGESG24

Green

WGECR24, WGESR24

Red

NOTICE: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS: 16-33V. THIS PRODUCT WAS ONLY TESTED TO THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM

OPERATION.

1 When using products manufactured after 7-1-10, these values are to be used when calculating current draws.

12VDC CLEAR Lens Strobe Current Ratings

Use with GEC3-12 and GES3-12 Products

Candela

Regulated 12VDC

Max. Operating

Current (mA)

Regulated 12VFWR

Max. Operating

Current (mA)

1

15

92

145

30

141

224

60

260

459

75

312

460

NOTICE: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS: 16-33V. THIS PRODUCT WAS ONLY TESTED TO THE

STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM OPERATION.

1

When using products manufactured after 7-1-10, these values are to be used when calculating current draws.

24VDC CLEAR & AMBER Lens Outdoor

Strobe Current Ratings

Use with WGEC24, WGES24,

WGECA24, WGESA24 Products

Candela

Regulated 24VDC

Max. Operating

Current (mA)

Regulated 24VFWR

Max. Operating

Current (mA)

1

75

170

263

24VDC BLUE, GREEN & RED Lens Outdoor

Strobe Current Ratings

Use with WGECB24, WGESB24, WGECG24,

WGESG24, WGECR24, WGESR24 Products

Candela

Regulated 24VDC

Max. Operating

Current (mA)

Regulated 24VFWR

Max. Operating

Current (mA)

1

75

164

278

AMBER Lens Indoor Strobe Current Ratings

Use with GECA24 and GESA24 Products

Candela

Regulated 24VDC

Max. Operating

Current (mA)

Regulated 24VFWR

Max. Operating

Current (mA)

1

15

47

82

30

64

112

60

113

178

75

145

213

110

178

259

GECA24, GESA24, GECB24, GESB24, GECG24, GESG24, GECR24, GESR24 PRODUCT INFORMATION

BLUE, GREEN & RED Lens Indoor

Strobe Current Ratings

Use with GECB24, GESB24, GECG24,

GESG24, GECR24, GESR24 Products

Candela

Regulated 24VDC

Max. Operating

Current (mA)

Regulated 24VFWR

Max. Operating

Current (mA)

1

15

105

164

30

130

196

60

203

325

75

243

355

110

310

491

Models

Color Lens

GECA24, GESA24

Amber

GECB24, GESB24

Blue

GECG24, GESG24

Green

GECR24, GESR24

Red

NOTICE: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS: 16-33V. THIS PRODUCT WAS ONLY TESTED TO THE

STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM OPERATION.

1

When using products manufactured after 7-1-10, these values are to be used when calculating current draws.

Horn Decibel Levels

Horn Current Ratings Over

Input Voltage Range of 16-33V

Horn Mode

Minimum SPL

at 10Ft. Per

ANSI/UL 464

(HIGH)

Minimum SPL

at 10Ft. Per

ANSI/UL 464

(LOW)

Regulated 24VDC

Max. Operating

Current (mA)

HIGH Setting

Regulated 24VFWR

Max. Operating

Current (mA)

HIGH Setting

Temp 3 2400Hz

78 dBA

71* dBA

28

48

Temp 3 Mechanical

76 dBA

70* dBA

25

44

Temp 3 Chime

70* dBA

66* dBA

15

30

Continuous 2400Hz

81 dBA

74* dBA

28

48

Continuous Mechanical

80 dBA

72* dBA

25

44

Continuous Chime

70* dBA

66* dBA

15

30

Whoop

82 dBA

69* dBA

56

62

HORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION

Horn Decibel Levels

Horn Current Ratings Over

Input Voltage Range of 8-17.5V

Horn Mode

Minimum SPL

at 10Ft. Per

ANSI/UL 464

(HIGH)

Minimum SPL

at 10Ft. Per

ANSI/UL 464

(LOW)

Regulated 12VDC

Max. Operating

Current (mA)

HIGH Setting

Regulated 12VFWR

Max. Operating

Current (mA)

HIGH Setting

Temp 3 2400Hz

76 dBA

69* dBA

29

48

Temp 3 Mechanical

75 dBA

68* dBA

26

45

Temp 3 Chime

62* dBA

60* dBA

13

24

Continuous 2400Hz

79 dBA

74* dBA

29

48

Continuous Mechanical

78 dBA

72* dBA

26

45

Continuous Chime

63* dBA

61* dBA

13

24

Whoop

78 dBA

71* dBA

55

61

NOTICE:

THE THREE PULSE TEMPORAL PATTERN IS TO BE USED FOR EVACUATION USE ONLY.

THE SOUND OUTPUT FOR THE TEMPORAL 3 TONE IS RATED LOWER SINCE THE TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND OUT PUT RATING. WHILE THE HORN IS PRODUCING A TONE

IN THE TEMPORAL 3 MODE ITS SOUND PRESSURE IS THE SAME AS THE CONTINUOUS MODE. UNITS HAVE BEEN TESTED TO 0°C, 49°C AND 93% HUMIDITY.

* Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 sound level required for public mode fire protection service.

These settings are acceptable only for private mode fire alarm signaling use. Use the high dBA setting for public mode applications (the chime tone is always private mode).

550-0011

Page 2

Strobe light can not be seen when objects such as doors, furniture or walls block strobe light.

NOTICE:

THE VISUAL SIGNAL MUST BE IN THE DIRECT VIEWING AREA OF THE OCCUPANT IN ORDER TO BE SEEN.

VISUAL SIGNALS FOR THE HEARING IMPAIRED ARE ONLY ONE METHOD OF ALERTING THE HEARING IMPAIRED. VISUAL SIGNALS MAY NOT BE THE PREFERRED METHOD

FOR NOTIFYING ALL HEARING IMPAIRED INDIVIDUALS.

THE STROBE LIGHT MUST BE SEEN BY THE SLEEPING PERSON. IF THE PERSON HAS HEAD TURNED OR OTHERWISE UNABLE TO BE ALERTED BY VISUAL, THE STROBE

WILL NOT BE EFFECTIVE.

Advertising
This manual is related to the following products: