IV. WIRING

Wiring for synchronized strobes and horns.

Using this method you may:

Use only two wires to synchronize the temporal horn and strobe with the ability to mute the horn (place

switches 1 and 2 in the ON position on the GEC24, GEC3-24, GEC3-12, WGEC24, GECA24, GECB24,

GECG24, GECR24, WGECA24, WGECB24, WGECG24, WGECR24).

Mute the horn only when the temporal horn option has been selected.

Use the Gentex synchronization protocol to provide synchronization and mute the horn, if available.

Wiring for synchronized parallel (unison) horn/strobe operation.

Using this method you may:

Use four wires where two wires are used to power and synchronize the strobe and two additional wires

are used to power and synchronize the horn (place switches 1 and 2 in the OFF position on the GEC24,

GEC3-24, GEC3-12, WGEC24, GECA24, GECB24, GECG24, GECR24, WGECA24, WGECB24,

WGECG24, WGECR24).

Choose either continuous horn and allow the FACP to control the horn or choose temporal horn and synchronize the horns with the Gentex synchronization protocol.

Use the Gentex synchronization protocol to provide synchronization and mute the horn, if available.

NOTICE:

FOR THIS OPTION, SWITCHES 1 AND 2 ON THE GEC24, GEC3-24, GEC3-12, WGEC24, GECA24, GECB24, GECG24, GECR24, WGECA24, WGECB24, WGEC24, WGECR24 MUST

BE IN THE OFF POSITION TO ISOLATE POWER TO THE AUDIBLE AND VISIBLE PORTION OF THE CIRCUIT.

ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE. THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR PULSING

SIGNALING CIRCUITS. HOWEVER, USE OF THE AVSM CONTROL MODULE IS PERMITTED TO SYNCHRONIZE THE STROBE AND/OR MUTE THE HORN.

REFERENCE AVSM CONTROL MODULE MANUAL (550-0284, DATED 2-1-03) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM MANUAL CAN BE OBTAINED AT

HTTP://WWW.GENTEX.COM OR CALL GENTEX CORPORATION AT 1-800-436-8391.

Conventional Method:

You may connect both the strobe and the horn directly from a source of rated power without the use of a control module. However, the horns and strobe lights will NOT be synchronized. Place

switches 1 and 2 in the ON position on the GEC24, GEC3-24, GEC3-12, WGEC24, GECA24, GECB24, GECG24, GECR24, WGECA24, WGECB24, WGECG24, WGECR24 to power both the

audible and visible from a single pair of power wires. If you wish to power the horn and strobe from independent sources of power, place switches 1 and 2 in the OFF position on the GEC24,

GEC3-24, GEC3-12, WGEC24, GECA24, GECB24, GECG24, GECR24, WGECA24, WGECB24, WGECG24, WGECR24 and connect power to the appropriate terminals.

CAUTION: When using only a single power source to

energize the strobe and horn (switches 1 and 2 in the ON

position), the in/out wiring must be under the S+ and S-

terminals only. Failure to do so may result in damage to your

signal. For the horn only (GEH24 and GEH12) and strobe only

(GES24, GES3-24, GES3-12, WGES24, GESA24, GESB24,

GESG24, GESR24, WGESA24, WGESB24, WGESG24,

WGESR24), only the top three terminals are to be used.

SWITCH POSITION

TONE

3

4

5

Mechanical Temporal 3

ON

ON

ON

Mechanical - Continuous

OFF

ON

ON

2400Hz - Temporal 3

ON

OFF

ON

2400Hz - Continuous

OFF

OFF

ON

Chime - Temporal 3

ON

ON

OFF

Chime - Continuous

OFF

ON

OFF

Whoop

ON

OFF

OFF

Whoop

OFF

OFF

OFF

NOTICE:

SWITCH POSITIONS 1 AND 2 IN THE OFF POSITION TO

SELECT ISOLATED HORN AND STROBE POWER INPUTS

SWITCH POSITION 6 ON = HIGH DBA

SWITCH POSITION 6 OFF = LOW DBA

CAUTION: A jumper card is provided to test for correct

wiring in the supervisory mode only. DO NOT pass alarm

current through the jumper.

Gentex Super-Slide

®

Mounting Bracket:

Allows the installer to pre-wire the system, test for system

supervision, remove the signal head until occupancy,

switch out Gentex signals without changing mounting

brackets and has locking edge connector for snap-in-place

installation.

Gentex Checkmate

®

Instant Voltage Verification:

It is often necessary to confirm the voltage drop along a

line of devices. The access holes are provided in the back

of the terminal block to allow the voltage to be measured

directly without removing the device. Typically this would

be done at the end of the line to confirm design criteria.

Most measurements will be taken using the S+ and S-

locations although access is provided to other locations.
NOTICE: CARE SHOULD BE TAKEN TO NOT SHORT

THE TEST PROBES.