Operation, Maintenance – Campbell Hausfeld FP2003 User Manual

Page 21

Advertising
background image

21 Sp

4

ASME SAFETY VALVE

Do not remove or
attempt to adjust

the safety valve!

Check safetly valve under pressure daily
by pulling the ring by hand. If air leaks
after ring has been released, or valve is
stuck and cannot be actuated by ring, it
MUST be replaced.

REGULATOR KNOB

1. This knob controls air pressure to an

air operated tool or paint spray gun.

2. Turn knob clockwise to increase air

pressure.

3. To lower air pressure turn knob

counterclockwise.

4. Turn fully counterclockwise to shut

off flow of air completely.

Disconnect power
source then release all
pressure from the
system before
attempting to install, service, relocate
or perform any maintenance.

Check compressor often for any visible
problems and follow maintenance
procedures each time compressor is
used.

1. Pull ring on safety valve and allow it

to snap back to normal position.

Safety valve must
be replaced if it

cannot be actuated or it leaks air after
ring is released.

2. Turn compressor off and release

pressure from system. Drain moisture
from tank by opening drain cock
underneath tank. Tilt tank to
remove all moisture.

3. Clean dust and dirt from motor, tank,

air lines and pump cooling fins while
compressor is still OFF.

LUBRICATION

This is an oilless type compressor
requiring no lubrication.

THERMAL OVERLOAD PROTECTOR

This compressor is
equipped with an

automatic reset thermal overload
protector which will shut off motor if it
becomes overheated.

If thermal overload protector shuts
motor OFF frequently, look for the
following causes.

1. Low voltage.

2. Clogged air filter.

3. Lack of proper ventilation.

If the thermal
overload protector

is actuated, the motor must be allowed
to cool down before start-up is possible.
The motor will automatically restart
without warning if left plugged into
electrical outlet and unit is turned on.

STORAGE

1. When not in use, store hose and

compressor in a cool dry place.

2. Drain tank of moisture.

3. Disconnect hose and hang open ends

down to allow any moisture to drain.

Figure 3

MOISTURE IN COMPRESSED AIR

Moisture in compressed air will form into droplets as it comes from an air
compressor pump. When humidity is high or when a compressor is in continuous
use for an extended period of time, this moisture will collect in the tank. When
using a paint spray or sandblast gun, this water will be carried from the tank
through the hose, and out of the gun as droplets mixed with the spray material.

IMPORTANT: This condensation will cause water spots in a paint job, especially
when spraying other than water based paints. If sandblasting, it will cause the
sand to cake and clog the gun, rendering it ineffective. A filter in the air line
(MP3105), located as near to the gun as possible, will help eliminate this
moisture.

Operation

(Continued)

Oilless Compressors

Maintenance

Figure 4

www.campbellhausfeld.com

FP2003

Guía de diagnóstico de averías

Problema

Posible(s) Causa(s)

Acción a tomar

1. No hay corriente eléctrica, o el

interruptor está en OFF (apagado)

2. El fusible está quemado (en estos

casos generalmente la luz del
interruptor no se enciende)

3. El motor está sobrecargado

4. La presión del tanque está al máximo
5. El cortacircuito (cuchilla) está abierto

6. El presostato está dañado

1. Tamaño incorrecto de fusible,

circuito sobrecargado

2. Válvula de retención defectuosas

1. Bajo voltaje

2. Falta de ventilación adecuada o

temperatura ambiente muy alta

3. Compruebe si la válvula no funciona

bien

4. Fallaron las válvulas del compresor

1. Pernos flojos, tanque no nivelado
2. Cojinete defectuoso en la excéntrica

o en el eje del motor

3. Cilindro o anillo de émbolo gastados

o rayados

1. Cerciórese de que el compresor esté conectado al

tomacorriente y el interruptor esté en ON
(encendido)

2. Desconecte el compresor del tomacorriente y

destape el cabezal. Reemplace el fusible (pieza No.
FP200352AV)

3. Permita que el compresor se enfríe por

aproximadamente 30 minutos de modo que el
dispositivo de sobrecarga térmica se reactive. Si la
unidad aún no se enciende, vacíe el aire del tanque
y regrese a los pasos 1 y 2

4. Libere el aire del tanque
5. Cierre el cortacircuito y determine la causa del

problema

6. Re el cabezal

1. Verifique que el fusible sea el adecuado (5 amp),

utilice un fusible de tiempo retardado. Desconecte
otros artefactos
eléctricos del circuito o haga funcionar el compresor
con su propio circuito derivado

2. Reemplace el ensamblaje de la válvula de chequeo

No desarme la válvula

de retención con aire

en el tanque; purgue el tanque

1. Elimine el cordón de extensión, revise con un

voltímetro

2. Mueva el compresor a una zona bien ventilada

3. Reemplace el ensamblaje de la válvula de chequeo

4. Re el cabezal

No desarme la válvula
de retención con aire

en el tanque; purgue el tanque

1. Ajuste los pernos, calce el tanque para nivelarlo
2. Re el cabezal

3. Re el cabezal

!

PELIGRO

!

PELIGRO

El compresor no
funciona

Los fusibles vuelan o el
interruptor de circuito
se desconecta
repetidamente

Nunca use un cordón
de extensión con
este producto

El protector de
sobrecarga térmica se
activa repetidamente

Golpeteos, cascabeleos,
vibración excesiva

!

PRECAUCION

Advertising