tekmar 156 Difference Setpoint Control User Manual

Data brochure, D 156, Difference setpoint control 156

Advertising
background image

1

of

12

©

2010 D

156

-

06/10

D 156

06/10

- Data Brochure

Difference Setpoint Control 156

The Difference Setpoint Control 156 is designed to operate an on/off pump to transfer heat from a heat source to a storage
tank. The control operates based on a setpoint temperature difference (ΔT). The relay turns on when the ΔT rises above
the setpoint and turns off when the ΔT falls below the setpoint less the differential. The Source Minimum and Storage
Maximum settings turn off the relay when heat transfer is no longer desirable. Potential applications include using solar
collectors or a wood boiler as a heat source.

Additional functions include:

24 V (ac) OR 24 V (dc) power supply
Monitor Minimum & Maximum temperatures for Source & Storage
Displays number of running hours of the relay
Displays ΔT• hours to perform energy calculation
CSA and UL certified for use in the USA and Canada
NEW Solar Sensor 085 immersion type sensor included!






Difference Setpoint
Control 156

On / Off

Item

Dat

e Code

Power: 24 V (ac) ±10% 50/60 Hz 3 VA

24 V (dc) ±10% 0.03 A

Relay: 240 V (ac) 10 A 1/3 hp

tektra 906-12

Meets Class B:
Canadian ICES
FCC Part 15

ΔT

Source

Maximum

Minimum

Storage

ΔT • hours

Diff’l

1

2

3

4

C

R

5

Com

6

Src

7

Stor

No Power

Signal wiring must be

rated at least 300V

Made in Canada

Power

Relay

H30

10

B

Input
Universal Sensor
Included

Input

Solar Sensor

Included

Output

Primary

Pump

Input

24 V (ac or dc)