MAXIMUM STORAGE SETPOINT

If the measured storage temperature rises above the Maximum Storage Setpoint, the relay is turned off. The relay remains
off until the storage temperature drops below the Maximum Storage Setpoint less the Maximum Storage Differential.

The Maximum Storage Setpoint stops the transfer of heat when the storage temperature rises above the Maximum
Storage Setpoint, which prevents the storage tank from over heating. Turning off the relay allows heat to be drawn out of
the tank to satisfy any heating loads without heat being returned to the tank from the heat source, thus lowering the tank
temperature.

Relay operation showing the
turn on and turn off points with
respect to the Max Storage
Setpoint and Differential.

Relay operation showing the
turn on and turn off points with
respect to the Min Source
Setpoint and Differential.

Min Source
Differential

Min Source
Setpoint

ON

ON

OFF

OFF

OFF

Increasing Time

Increasing

T

e

mper

ature

Increasing Time

MINIMUM SOURCE SETPOINT

If the measured source temperature drops below the Minimum Source Setpoint, the relay is turned off. The relay remains
off until the source temperature rises above the Minimum Source Setpoint plus the Minimum Source Differential.

The Source Minimum Setpoint does not provide freeze protection; it only stops the transfer of heat when the source
temperature falls below the Minimum Source Setpoint. The heat source is still susceptible to freezing. Turning off the relay
allows the heat source to gain heat by stopping the heat transfer to the storage tank.

Max Storage
Differential

Max Storage
Setpoint

ON

ON

ON

OFF

OFF

Increasing Time

Increasing

T

e

mper

ature

Increasing Time

ΔT SETPOINT

The control measures the difference between the source and the storage temperatures (ΔT). When the measured ΔT is
greater than the ΔT setpoint, the relay is turned on to transfer heat from the source to the storage. If the ΔT drops below
the ΔT Setpoint less the ΔT Differential, the relay is turned off.

ΔT Differential

ΔT

Setpoint

ON

ON

OFF

OFF

OFF

Increasing Time

Increasing ΔT

Relay operation showing
the turn on and turn off
points with respect to the ΔT
Setpoint and ΔT Differential.

Typical Settings

ΔT Setpoint

Differential

With a heat exchanger

15 to 25°F (8 to 14°C)

10 to 15°F

(6 to 8°C)

Without a heat exchanger

13 to 21°F (7 to 12°C)