View Menu (1 of 1)

Outdoor - Current outdoor air temperature as measured by the
outdoor sensor.

-67 to 149°F
(-55 to 65°C)

Boiler Supply - Current boiler supply water temperature as measured
by the boiler supply sensor.

This item is available in all modes.

14 to 266°F
(-10 to 130°C)

D1

E1
F1

Boiler Target - Boiler target temperature is the temperature the
control is currently trying to maintain at the boiler supply sensor + /
– ½ of the differential.

This item is available in all modes.

– – –, 14 to 266°F
(– – –, -10 to 130°C)

Boiler Return - Current boiler return water temperature as measured
by the boiler return sensor.

A boiler return sensor must be installed to view this item. This item is
available in all modes.

14 to 266°F
(-10 to 130°C)

Delta T - Current difference in temperature between the boiler supply
sensor and the boiler return sensor temperatures.

A boiler return sensor must be installed to view this item. This item is
available in all modes.

0 to 252°F
(0 to 140°C)

A

Boiler 1 Hours - The total running time of boiler 1 since this item was
last cleared.

To clear this item, press the

and

button simultaneously while

viewing this item. This item is available in all modes.

0 to 1999 hr

A

Boiler 2 Hours - The total running time of boiler 2 since this item was
last cleared.

To clear this item, press the

and

button simultaneously while

viewing this item. This item is available in modes 1 to 3.

0 to 1999 hr

A

Boiler 3 Hours - The total running time of boiler 3 since this item was
last cleared.

To clear this item, press the

and

button simultaneously while

viewing this item. This item is available in mode 1.

0 to 1999 hr

A

Boiler 4 Hours - The total running time of boiler 4 since this item was
last cleared.

To clear this item, press the

and

button simultaneously while

viewing this item. This item is available in mode 1.

0 to 1999 hr