Monitor menu, Schd (schedule) menu, Misc. menu – tekmar 362 Mixing Control User Manuals User Manual

Page 3: Rtu menus, Rtu - view menu

Advertising
background image

3 of 4

Copyright © 1999 U 362 -06/99

Room Temperature Unit (RTU) 062, 063

A single RTU can be connected to the Mixing Control 362 in order to provide the control with indoor
temperature feedback for the mixing side of the heating system (Refer to Essay E 002). When using an
RTU, several items related to the mixing side of the heating system are no longer available in the control’s
User Interface. These items are available only in the RTU’s User Interface. Also, the number of items that
are available on the RTU depends on the type of RTU that is connected to the control.

-67 to 149˚F
(-55 to 65˚C)

-67 to 149˚F
(-55 to 65˚C)

The highest recorded temperature at the slab sensor since this item
was last cleared. To clear this item, press both the and buttons
until ”CLR” is displayed.

The lowest recorded temperature at the slab sensor since this item
was last cleared. To clear this item, press both the and buttons
until ”CLR” is displayed.

-58 to 167˚F
(-50 to 75˚C)

-58 to 167˚F
(-50 to 75˚C)

362 Monitor Menu

Item

LT

D

USER

Range

The highest outdoor air temperature recorded since this item was
last cleared. To clear this item, press and hold the and buttons
until ‘CLR’ is displayed.

The lowest outdoor air temperature recorded since this item was
last cleared. To clear this item, press and hold the and buttons
until ‘CLR’ is displayed.

NONE, TMPY Occ, PERM
Occ, TMPY UnOcc, PERM
UnOcc, AWAY

362 Schd (Schedule) Menu

Item

LT

D

USER

Range

None – No override. TMPY Occ – Overrides to Occupied setting for 3 hours. PERM Occ – Overrides to Occupied setting until new
override is selected.

TMPY UnOcc - Overrides to UnOccupied for 3 hours. PERM UnOcc – Overrides to UnOccupied setting until

new override is selected.

AWAY – Room & WWSD temperature at 62

°F (17°C), no DHW.

The type of setback override that is in effect.

DIP switch =

Setback

AWAY is available even if DIP

≠ Setback

The units of measurement in which all of the temperatures are to be
displayed by the control.

˚F, ˚C

The operating mode for the back lighting of the LCD and the time
until the control returns to the view menu after any button was
pressed.

If Backlight is set to OFF, the control returns after 10

seconds and the backlight stays off.

If Backlight is set to 30 SEC,

the control returns after 30 seconds and the backlight stays on for
30 seconds after any button press.

If Backlight is set to ON, the

control returns after 90 seconds and the backlight stays on.

OFF, 30

sec, ON

The access level that is to be used by the control.
DIP switch =
Only qualified service people should adjust items in the ADV (Advance)
and INST (Installer) access levels.

ADV, INST, USER, LTD

362 Misc (Miscellaneous) Menu

Item

LT

D

USER

Range

Item

Menu

UnOcc 1

°F

View

Heat

35 to 100˚F
(2 to 38˚C)

Current room air temperature.

14 to 167˚F
(-10 to 75˚C)

Target room air temperature.

-67 to 149

°F

(-55 to 65

°C)

Current slab sensor temperature. This item is only available if a
tekmar slab sensor is connected to a RTU 063.

-58 to 167

°F

(-50 to 75

°C)

362 RTU View Menu

Item

LT

D

USER

Range

062 063

Current outdoor air temperature as measured by the outdoor sensor.

Note: Depending on the settings the installer make in the control, certain menu items may not appear.