Section C: DHW Operation

Section C1: Domestic Hot Water (DHW)

DHW DEMAND

A

DHW Demand is required in order for the control to provide heat to the DHW system. A

DHW aquastat or setpoint control is used as a switch in the DHW demand circuit. Once
the control detects a DHW demand, the

DHW Demand pointer turns on in the LCD and the

control operates the boiler to provide a sufficient boiler supply water temperature to the
DHW tank. The control operates the pumps as described below.

The control registers a

DHW Demand when a voltage between 24 and 230 V (ac) is applied

across the

DHW Dem and Com Dem terminals (29 and 31).

BOILER TARGET DURING DHW GENERATION

The boiler target

temperature is at least as hot as the DHW exchange setting (DHW XCHG). The DHW demand overrides the boiler

reset target temperature, except when the boiler reset target is higher than the DHW exchange setting.

DHW MODE AND PRIORITY OPERATION

The control has four different settings available for DHW MODE. The required DHW MODE setting will depend on the piping
arrangement of the DHW tank. It is often desirable to limit or even stop the flow of heat to the heating system when the DHW tank
calls for heat. This allows for a faster recovery of the DHW tank.

DHW MODE 1 - DHW in Parallel no Priority

When a

DHW Demand is present, the DHW Pmp / Vlv contact closes.

The primary pump (

Prim P1) does not turn on, but may operate based

on either a Boiler Demand, Mixing Demand or a Setpoint Demand.
Refer to sections B and D.

It is assumed that the DHW pump will provide adequate flow
through the heat exchanger and the boiler.

DHW MODE 2 - DHW in Parallel with Priority

When a

DHW Demand is present, the DHW Pmp / Vlv contact closes

and the primary pump (

Prim P1) contact is opened.

It is assumed that the DHW pump will provide adequate flow
through the heat exchanger and the boiler.

DHW MODE 3 - DHW in Primary / Secondary no Priority

When a

DHW Demand is present, the DHW Pmp / Vlv contact is

closed and the primary pump (

Prim P1) is operated.

This mode can be used if a DHW tank is piped in direct return and
a DHW valve is installed.

30

Boil

Dem

31

Com

Dem

29

DHW

Dem

24 to 230 V (ac)

Aquastat

DHW Pump

Primary

Pump

DHW Pump

Primary

Pump

DHW Pump

Primary

Pump