tekmar 664 Snow Detector & Melting Control Installation User Manual

Data brochure, D 664, Snow detector & melting control 664

Advertising
background image

1

of

36

©

2009 D

664

-

07/09

- Data Brochure

Snow Detector & Melting Control 664

D 664

07/09

The Snow Detector and Melting Control 664 is designed to control up to two zones in a snow melting system. The control automatically
adjusts the mixed supply water to the snow melting system by controlling up to two boilers and a single mixing device. For mixing, the
664 can use a variable speed injection pump, a fl oating action mixing valve or a 4-20 mA device. The snow melting system may be
started manually or automatically through the use of a Snow / Ice Sensor 090. The 664 control includes a large Liquid Crystal Display
(LCD) in order to view system status and operating information.

Additional features include:

1

+

2

3

Opn/

4-20 mA

Var

4

Pwr

Mix

5

Cls

6

Red

7

Blk/

Com

8

Blu

9

Yel

10

Brn/

Slab1

11

Slab

2

12

Com

13

tN2

14

Mix
Ret

15

Mix

Sup

16

Com

17

Boil

18

Out

19

Melt/Idle
Demand

20 21

1

22 23

2

24 25

Zn

1

26

Com

Zn

27

Zn

2

28

30

Sys

P1

29

Power

L

N

Menu

Test

Snow Detector & Melting Control 664

Two Zone, Two Stage Boiler, Mixing

Item

Start

Stop

Idle Demand

Signal wiring must be rated at least 300 V.

Melt Demand

not testing

testing

testing paused

For maximum heat,
press and hold Test
button for 3 seconds.

Made in Canada by
tekmar Control Systems Ltd.
tektra 900-01

Power

115 V ± 10% 50/60 Hz 600 VA

Relays

230 V (ac) 5 A 1/6 hp

Stage/Zn/P1 Relays 230 V (ac) 5 A 1/3 hp
Var. Pump

230 V (ac) 2.4 A max (FLA)

5 A max (LRA), fuse T2.5 A 250V

Demand

20 to 260 V (ac) 2 VA

Meets Class B:
Canadian ICES
FCC Part 15

off

red

red

Do not apply power

1 kΩ max

%

Output

4-20 mA

device

Output

Variable

Speed

driven

pump

Output

Mixing

Valve &

Actuating

Motor

Input

Snow/Ice Sensor

090 installed with

Sensor Socket

091 Optional

Input

Slab

Sensor

Optional

Input

Remote Display Module (RDM)

or

Remote Start / Stop Module

Slab

Sensor

Optional

OR

OR

or

OR

OR

Input

Universal

Sensor

Included

Input

Universal

Sensor

Included

Input

Universal

Sensor

Included

Input

Outdoor

Sensor

Included

Input

Melt/Idle
Demand

Output
Boiler

Output
Boiler

Output
Zone
Pumps

Zone Valves

Output
System
Pump

Input
115 V (ac)
Power
Supply

OR

Melt Demand

Idle Demand

WWSD

Minimum

Maximum

Water

Melting

M

H1

198D

Stage

Stage

• Temporary

Idle

Optional priority zoning operation

Slab protection for the snow melting system

• Boiler

protection

• Manual

Override

Adjustable Warm Weather Shut Down (WWSD)

Cold Weather Cut Out (CWCO)

Remote display and adjustment capabilities

Test sequence to ensure proper component operation

Pump and valve exercising

CSA C US Certifi ed (approved to applicable UL standards)