Item field access level description range – tekmar 664 Snow Detector & Melting Control Installation User Manual

Page 23

Advertising
background image

23 of 36

©

2009 D

664

-

07/09

Item Field

Access
Level

Description

Range

Actual

Setting

Section

LT

D

USER

INS

T

AD

V

664 Adjust Menu (1 of 3)

B1

Run Time The time for which a zone is operated
once it has reached its melting temperature. This
item cannot be viewed if a Remote Start / Stop
Module 039 has been connected.

0:30 to 17:00 hr,
INF (Infi nity)
Default = 4:00 hr

E1

Add Melt The additional time for which a zone
is operated once the Snow / Ice Sensor 090
becomes dry.
090 is present

0:00 to 6:00 hr
Default = 0:30 hr

D1

Sensitivity Sensitivity of water detection of the
Snow / Ice Sensor 090.
090 is present

AUTO, 20 to 80%
Default = AUTO

E1

Zone 1 Selects zone 1 as operational or not.

OFF, AUTO
Default = AUTO

E1

Melt 1 The desired slab surface temperature of
zone 1 while in the Melting mode.
Zone 1 = AUTO

32 to 95°F
(0 to 35°C)
Default = 36°F (2°C)

F1

Idle 1 The desired slab surface temperature of
zone 1 while in the Idling mode.
Zone 1 = AUTO

OFF, 20 to 95°F
(OFF, -7 to 35°C)
Default = OFF

E1

Zone 2 Selects zone 2 as operational or not.

OFF, AUTO
Default = OFF

A

C1

Boil Supply Current boiler supply water temperature as
measured by the boiler sensor.
Boil SENS = SUP

-31 to 266°F
(-35 to 130°C)

A

C2

Boil Return Current boiler return water temperature as
measured by the boiler sensor.
Boil SENS = RET

-31 to 266°F
(-35 to 130°C)

Item Field

Access
Level

Description

Range

Section

LT

D

USER

INS

T

AD

V

664 View Menu (2 of 2)