Settings – tekmar 132 Pump Sequencer User Manual

Page 8

Advertising
background image

©

2010 D

132

-

04/10

8

of

12

Connecting The Control

---------------------------------------------------------

Make sure all power to the devices and terminal blocks is off, and remove any
remaining jumpers from the terminals.

Reconnect the terminal blocks to the control by carefully aligning them with their respec-
tive headers on the control and then pushing the terminal blocks into the headers. The
terminal blocks should snap firmly into place.

Install the supplied safety dividers between the unpowered sensor input and the pow-
ered 120 V (ac) or 24 V (ac) wiring chambers.

Apply power to the control. The operation of the control on power up is described in the
Sequence of Operation section of this brochure.

WARM WEATHER SHUT DOWN (WWSD) ---------------------------------------------------

---------------------------------------------------

The WWSD dial is only operational when an outdoor sensor is installed. The WWSD dial
can be set from 35 to 100°F or Off (2 to 38°C or Off). Refer to section A.

Note: If an outdoor sensor is not installed, the WWSD dial must be set to Off.

FREQUENCY OF ROTATION ---------------------------------------------------------------------

---------------------------------------------------------------------

The Frequency of Rotation dial can be set from 12 to 168 hours or Off. Refer to section A.

30 second Delay / 10 second Delay

-----------------------------------------------------------------------------------

The 30 second Delay / 10 second Delay DIP switch is used to select what time delay is required to prove flow once a pump
contact is turned on. Refer to section A.

Exercising / Off

---------------------------------------------------------------------------------------------------------

The Exercising / Off DIP switch is used to select exercising. If the DIP switch is set to Exercising, refer to section A.

Alert per Pump / Alert Levels

-----------------------------------------------------------------------------------------

The Alert per Pump / Alert Levels DIP switch is used to select which mode of alert operation is required. Refer to section C.

Settings

13 14

16

15

A A

Alert

Alert

B B

WWSD

35

Off

70° F

100

Frequency of Rotation

12

Off

96 hours

168

48

144

2-Stage

Alert Levels

Pump

1 2

Auto

30 second Delay

Exercising
Alert per Pump

Off

10 second Delay

Off

Stand-by

DIP SWITCH SETTINGS ----------------------------------------------------------------------------------------------------------------------------

----------------------------------------------------------------------------------------------------------------------------

Pump 1 Auto / Off

-----------------------------------------------------------------

The Pump 1 Auto / Off DIP switch is used to select pump 1 operation. If the DIP switch
is set to Pump 1 Auto, refer to section B.

Pump 2 Auto / Off

----------------------------------------------------------------

The Pump 2 Auto / Off DIP switch is used to select pump 2 operation. If the DIP switch
is set to Pump 2 Auto, refer to section B.

2-Stage / Stand-by

---------------------------------------------------------------

The 2-Stage / Stand-by DIP switch is used to select which mode of pump control is
required. If 2-Stage is selected, refer to section B2, and if Stand-by is selected, refer to
section B1.