WSHP OPEN WIRING — The WSHP Open controller will

be factory mounted to the unit control panel and wired to the

Complete C or Deluxe D control board, however, the system

wiring will need to be completed utilizing WSHP Open con-

troller wiring diagrams and the Third Party Integration (TPI)

Guide. Factory installation includes harness, LWT (leaving

water temperature), supply air, and condensate sensor.

Wiring Sensors to Inputs — Sensors can be wired to the

WSHP Open controller’s inputs. See Table 7.
All field control wiring that connects to the WSHP Open con-

troller must be routed through the raceway built into the corner

post. The raceway provides the UL required clearance between

high and low-voltage wiring.

1. Pass control wires through hole provided in corner post.
2. Feed the wires through the raceway to the WSHP Open

controller.

3. Connect the wires to the removable Phoenix connectors.
4. Reconnect the connectors to the board.

Field-Supplied Sensor Hardware — The WSHP Open con-

troller is configurable with the following field-supplied sen-

sors. See Table 7.

Table 7 — Field-Supplied Sensors for

WSHP Open Controller

NOTE: BACview

6

Handheld or Virtual BACview can be used as the user

interface.

For specific details about sensors, refer to the literature sup-

plied with the sensor.
Wiring a SPT Sensor — A WSHP Open controller is connect-

ed to a wall-mounted space temperature (SPT) sensor to moni-

tor room temperature using a Molex plug.

The WSHP Open system offers the following SPT sensors.

See Table 8.

Table 8 — SPT Sensors

*The SPT Pro Plus fan speed adjustment has no effect in this application.

Wire SPT sensors to the WSHP Open controller’s Rnet port.

An Rnetbus can consist of any of the following combinations

of devices wired in a daisy-chain configuration:
• 1 SPT Plus, SPT Pro, or SPT Pro Plus sensor

• 1 to 4 SPT Standard sensors

• 1 to 4 SPT Standard sensors and 1 SPT Plus, SPT Pro, or

SPT Pro Plus sensor

• Any of the above combinations, plus up to 2 BACview

6

Handheld but no more than 6 total devices

NOTE: If the Rnetbus has multiple SPT Standard sensors, each

sensor must be given a unique address on the Rnetbus. See the

Carrier Open Sensor Installation Guide.
Use the specified type of wire and cable for maximum signal

integrity. See Table 9.

Table 9 — Rnet Wiring Specifications

LEGEND

To wire the SPT sensor to the controller:

1. Partially cut , then bend and pull off the outer jacket of

the Rnet cable(s), being careful not to nick the inner

insulation.

2. Strip about

1

/

4

in. of the inner insulation from each wire.

See Fig. 32.

WARNING

Disconnect all power to the unit before performing mainte-

nance or service. Unit may automatically start if power is

not disconnected. Failure to follow this warning could

cause personal injury, death, and/or equipment damage.

SENSOR

NOTES

Space Temperature Sensor

(SPT)

Field Installed (Must be used with

WSHP Open controller.)

Outdoor Air

Temperature Sensor

Network Sensor

Indoor Air Quality Sensor

(Separate Sensor)

Required only for demand

control ventilation.

Space Relative

Humidity Sensor

Separate Sensor

SENSOR

PART

NUMBER

FEATURES

SPT

Standard

SPS

• Local access port
• No operator control

SPT Plus

SPPL

• Slide potentiometer to adjust set point
• Manual on button to override schedule
• LED to show occupied status
• Local access port

SPT Pro

SPP

• LCD display
• Manual on button to override schedule
• Warmer and cooler buttons to adjust set point
• Info button to cycle through zone and outside

air temperatures, set points, and local override
time

• Local access port

SPT Pro

Plus

SPPF

• LCD display
• Manual on button to override schedule
• Warmer and cooler buttons to adjust set point
• Info button to cycle through zone and outside

air temperatures, set points, and local override
time

• Local access port
• Fan speed*

RNET WIRING SPECIFICATIONS

Description

4 conductor, unshielded, CMP,

plenum rated cable

Conductor

18 AWG

Maximum Length

500 ft

Recommended Coloring

Jacket: white

Wiring: black, white, green, red

UL Temperature

32 to 167 F

Voltage

300-vac, power limited

Listing

UL: NEC CL2P, or better

AWG — American Wire Gage
CMP — Communications Plenum Cable
NEC — National Electrical Code
UL

Underwriters Laboratories

Fig. 31 — Taco SBV Valve Wiring

Fig. 30 — AMV Valve Wiring

C

C

THERMOSTAT

1

Y

1

2

3

1

Y

AMV

TACO VALVE

HEATER SWITCH

a50-8441

a50-8442