8.0 OVERHEAT PROTECTION

8.1 The heater is equipped one (1) high limit thermocouple per

heating bank to sense the heating element sheath temperature.

Each high limit thermocouple must be wired to a separate Certified,

manual-reset high limit controller in the control panel. The set point

of the controller(s) must not exceed the values given in Table 2.

8.2 In the event of fan failure, excessive dust buildup, or restricted

airflow, the heater temperature may rise, causing the limit controls

to open and break the power supply to the heater.

CYCLING OF THE HEATER ON THE HIGH LIMITS

SHOULD NOT BE PERMITTED. Should this occur,

the system should be inspected to determine the

cause of the cycling, and the condition must be

corrected before regular operation is resumed.

9.0 MAINTENANCE

DISCONNECT ALL POWER TO THE EQUIPMENT

PRIOR TO SERVICING.

9.1 Periodically inspect the heater installation to ensure that all

connections, fitting, plugs, screws, covers, etc. are tight and free of

corrosion.

MI289 REV.2.01 Page 4 of 4

CCI Thermal Technologies Inc. 2721 Plymouth Drive, Oakville, ON L6H 5R5 Tel. (905) 829-4422 Fax (905) 829-4430

www.ccithermal.com

9.2 Check the surface of the duct section and terminal boxes for

dust and debris, especially after seasonal shutdowns. Clean with

a blast of air or vacuum.

9.3 Check the surface of the finned elements for dust and debris.

Clean with a blast of air.

9.4 Ensure that all fuses are in proper working order.

9.5 Maintain the pressure differential switch in accordance with the

manufacturer’s instructions.

9.6 Field repair of the heater should not be undertaken. In the

event that the heater must be repaired, contact the factory.

10.0 DRAWINGS AND LITERATURE

10.1 LITERATURE

The following manufacturer’s literature has been included with this

manual:

a)

Explosion-Proof Pressure Differential Switch

11.0 FIELD SERVICABILITY

The XDF explosion-proof duct heater is not field-serviceable. If

your heater requires servicing, please consult the factory.