OPERATION

GENERAL
1. To operate heater, make sure power supply is properly

connected as specified in the wiring schematic.

2. Ensure that the thermostat controlling the heater is set

above the ambient temperature.

3. During normal operation, the high-limit control should not

cycle the heater ON and OFF. If cycling occurs, check
to see if there is an airflow blockage. If there are no
obstructions, the heater must be examined by qualified
personnel to determine the cause of the high-limit cycling.

REPAIR AND REPLACEMENT

WARNING:

Disconnect heater from the power supply before opening enclosures or servicing heater. Lock the switch in

the “OFF” (open) position and/or tag the switch to prevent unexpected power application. This heater

should only be serviced by qualified personnel with electrical heating equipment experience.

Note: ONLY USE FACTORY SUPPLIED REPLACEMENT PARTS OF THE SAME SPECIFICATION.

HEATING ELEMENTS
1. Remove discharge grill from heater. Disconnect all wires

connected to the element terminals and remove all bus
bars. Remove element brackets from heater.

2. Remove elements, noting their proper placement.
3. Install factory-supplied replacement elements. Ensure that

the element brackets are in place and in good condition.

4. Reinstall all bus bars, wires, brackets, and discharge grill.

FAN
1. Remove grill from heater. Remove the screws securing

the fan to the fan hub attached to the motor.

2. Replace fan with factory-supplied fan.

TEMPERATURE HIGH-LIMIT
1. Remove discharge grill from heater.
2. Remove the wires connected to the high-limit.
3. Remove the screws securing the high-limit.
4. Install factory-supplied high-limit.
5. Reinstall wires, high-limit screws and discharge grill.

AIR INLET