0 dimensions and installation – CCI Thermal Technologies RXDF - Explosion-Proof Duct Heater User Manual

Page 2

Advertising
background image

CCI Thermal Technologies Inc. 2767 Brighton Road, Oakville, ON L6H 6J4 Tel. (905) 829-4422 Fax (905) 829-4430

www.ccithermal.com

MI289 REV.1 Page 2 of 4

Figure 1 - XDF Heater Dimensions

5.2

INSTALLATION

5.2.1

The heater is designed for installation in a horizontal duct

with the terminal boxes at the side. Improper orientation of the
duct heater could effect the safe and reliable operation of the heater.

IMPROPER ORIENTATION OF THE HEATER
COULD AFFECT THE SAFE AND RELIABLE
OPERATION OF THE HEATER.

NEVER USE THE CONTROL HOUSINGS FOR
LIFTING OR MOVING THE HEATER AS THIS
COULD DAMAGE THE HEATING ELEMENTS
AND CONDUIT.

5.2.2

To install the heater, bolt the heater assembly into the

customer supplied ducting system. If necessary, reinforce with duct
supports to support the heater weight as shown in Table 1. Note
proper orientation of heater, as shown by the "TOP" and "AIRFLOW"
labels.

5.2.3

An explosion-proof pressure differential switch has been

supplied loose. Install the switch in a suitable location and with
proper orientation. Install tubing between the switch and the duct
using the appropriate port on the switch body (sensing high or low
pressure). Consult manufacturer's operation instructions included
with this manual.

THE PRESSURE DIFFERENTIAL SWITCH IS A
CRITICAL SAFETY COMPONENT. IMPROPER
INSTALLATION OF THE SWITCH MAY RESULT
IN HAZARDOUS CONDITIONS.

4.3

Verify that the nameplate voltage, phase, and wattage are

as ordered and are the same as the electrical power supply
available.

DO NOT CONNECT THE HEATER TO AN
ELECTRICAL SUPPLY VOLTAGE OTHER
THAN THAT SHOWN ON THE PRODUCT
NAMEPLATE.

REVIEW THIS MANUAL AND ALL DRAWINGS
CONTAINED WITHIN PRIOR TO
INSTALLATION, WIRING, OR OPERATION OF
THE HEATER.

5.0

DIMENSIONS AND INSTALLATION

The heater must be installed by qualified personnel in strict
compliance with the electrical code and hazardous locations
standards.

THE HEATER MUST BE INSTALLED IN A
HORIZONTAL DUCT SECTION ONLY.
IMPROPER ORIENTATION OF THE HEATER
COULD AFFECT THE SAFE AND RELIABLE
OPERATION OF THE HEATER.

5.1

HEATER DIMENSIONS

Table 1 - Heater Dimensions and Weights (See Fig. 1)

Note: All dimension in millimeters (inches in brackets).

Duct Size

No. of

Weight

(W x H)

Banks

A

B

C

D

L

kg (lbs)

610 x 305

1

610

305

686

381

927

41 (90)

(24 x 12)

2

(24)

(12)

(27)

(15)

(36½)

73 (160)

762 x 457

1

762

457

838

533

1080

61 (135)

(30 x 18)

2

(30)

(18)

(33)

(21)

(42½)

114 (250)

914 x 610

1

914

610

991

686

1232

82 (180)

(36 x 24)

2

(36)

(24)

(39)

(27)

(48½)

148 (325)

Dimensions