8.0

OVERHEAT PROTECTION

8.1

The heater is equipped one (1) high limit thermocouple

per heating bank to sense the heating element sheath
temperature. Each high limit thermocouple must be wired to a
separate Certified, manual-reset high limit controller in the
control panel. The set point of the controller(s) must not exceed
the values given in Table 2.

8.2

In the event of fan failure, excessive dust buildup, or

restricted airflow, the heater temperature may rise, causing the limit
controls to open and break the power supply to the heater.

CYCLING OF THE HEATER ON THE HIGH
LIMITS SHOULD NOT BE PERMITTED. Should
this occur, the system should be inspected to
determine the cause of the cycling, and the
condition must be corrected before regular
operation is resumed.

9.0

MAINTENANCE

DISCONNECT ALL POWER TO THE
EQUIPMENT PRIOR TO SERVICING.

9.1

Periodically inspect the heater installation to ensure that all

connections, fitting, plugs, screws, covers, etc. are tight and free of
corrosion.

9.2

Check the surface of the duct section and terminal boxes

for dust and debris, especially after seasonal shutdowns. Clean
with a blast of air or vacuum.

9.3

Check the surface of the finned elements for dust and debris.

Clean with a blast of air.

9.4

Ensure that all fuses are in proper working order.

9.5

Maintain the pressure differential switch in accordance with

the manufacturer's instructions.

9.6

Field repair of the heater should not be undertaken. In the

event that the heater must be repaired, contact the factory.

10.0

DRAWINGS AND LITERATURE

10.1

LITERATURE

The following manufacturer's literature has been included with this
manual:

a)

Explosion-Proof Pressure Differential Switch

11.0

FIELD SERVICABILITY

The XDF explosion-proof duct heater is not field-serviceable. If
your heater requires servicing, please consult the factory.

WARRANTY

CCI Thermal Technologies Inc. warrants to the purchaser of each new product that any part thereof which proves to be defective in
material or workmanship under normal use within 24 months of the date of shipment or 12 months from the date of start of operation
(whichever occurs first) will be repaired or replaced without charge. Any such defect should be brought to the attention of the
company's office from which the product was purchased, which is authorized to furnish or replacement within the terms of this
warranty.

The Company will not be responsible for any expenses incurred in installation, removal from service, transportation cost, or damages
of any type whatsoever, including incidental or consequential damages. Some states or provinces do not allow exclusion or limitation
of incidental or consequential damages so the preceding exclusion or limitation may not be applicable to you.

Since we cannot anticipate or control the condition under which our products may be used, we accept no responsibility for the safety
and suitability of our products when used alone or in combination with other products. Tests for safety and suitability of the products
should be done by the user.

This warranty will not apply if, in the judgment of the Company damage or failure has resulted from accident, alteration, misuse,
abuse or operation on an incorrect power supply. The foregoing is in lieu of other warranties expressed or implied. CCI Thermal
Technologies Inc. neither assumes no authorizes any person to assume for it any other obligation, during transportation, installation
and operation or liability in connection with the said product.

Since the paint finish may be damaged during installation and operation, no warranty applies to such paint finish except for manufacturing
defects.

Heaters are not guaranteed against damage caused by corrosion.

Advertising