Heater maintenance checklist, Warning – CCI Thermal Technologies FE2 - Explosion-Proof Electric Air Unit Heater User Manual

Page 2

Advertising
background image

2

HEATER MAINTENANCE CHECKLIST

For Electric Forced Air Heaters

Heater Model: _________________________ Serial No.: ___________________________
Date of Maintenance: ___________________ Maintenance Done By: _________________
Comments: _________________________________________________________________
__________________________________________________________________________

WARNING

Disconnect heater from power supply at fuse box before opening enclosures or servicing heater.

Lock the switch in the “OFF” (open) position and/or tag the switch to prevent unexpected power application.

Verify that power has been disconnected at fuse box or main panel. Lock the switch in the “OFF” (open) position

and/or tag the switch to prevent unexpected power application.

This heater should only be serviced by personnel with heating and hazardous location equipment experience.

Photocopy

this page

for reuse.

Regular Service

Severe Service

Annual

Start Up

1 Month 3 Month

12

Month

Annual

Start Up

1 Month 3 Month

12

Month

Clean:

Finned Tubes

Fan

Fan Guard

Motor

Louvers

Remove dust using compressed air.

Do not immerse in water

or solvents.

X

X

X

Electrical

Check all terminal

connections and

conductors.

Tighten loose connections.

Replace conductors with damaged

insulation & frayed wiring.

For

drilling rigs, this should be done

with every rig re-location.

X

X

X

X

Inspect

contactor contacts.

If badly pitted, burned or welded

shut, replace with factory supplied

contactor.

For drilling rigs, this

should be done with every

rig re-location.

X

X

X

Check Fuses

are printed on the circuit board.

Always ensure a backup fuse is

available on the PCB.

For drilling

rigs, this should be done with

every rig re-location.

X

X

Mechanical

Inspect the Pressure Release Valve

label indicator for signs of rupture

and degradation. If any fluid

leakage occurs from the heater,

disconnect it from the power

supply and have the core replaced

immediately.

For drilling rigs,

this should be done with every

rig re-location.

X

X

X

Check all enclosures

must be clean, dry and free of

foreign materials.

For drilling

rigs, this should be done with

every rig re-location.

X

X

X

Check motor shaft

bearing play

If the motor does not run quietly

and smoothly and has excessive

play replace the motor.

For

drilling rigs, this should be done

with every rig re-location.

X

X

X

Check for

fluid leakage

Do not spray with water

or solvents.

The interiors of each enclosure

The Correct fuse rating and type

P R E V E N TAT I V E M A I N T E N A N C E G R I D