Fan rotation – CCI Thermal Technologies FE2 - Explosion-Proof Electric Air Unit Heater User Manual

Page 7

Advertising
background image

7

FIGURE 8

FIGURE 7A

FIGURE 6

Optional factory

installed built-in

room thermostat.

3. The internal grounding terminal in the control enclosure shall be

used as the equipment grounding means. An external bonding

terminal (see Figure 6) is provided for a supplementary bonding

connection where local authorities permit or require such a

connection.

FIGURE 7B

F I N A L I N S P E C T I O N

1. Before application of electrical power:
a. Check that all connections are secured and comply with the

applicable wiring diagram (see Figure 9) and code requirements,

b. Confirm that the power supply is compatible with the data plate

rating of the heater,

c. Remove any foreign objects from the heater,

d. Install all covers and verify that all enclosures are well secured, and

e. Ensure that the fan rotates freely. See Figure 6 for proper direction

of fan rotation.

Remote Room

Thermostat

if applicable

Terminals marked

“T’STAT”

Air
intake

Fan

rotation

Rear View of Heater

M25 or M32
opening for
field wiring

Motor
junction box

Control enclosure
and cover

Air exits through
louvers.

Connect supply conductors
to this side of contactor.

For a 1-phase heater, use
these contactor terminals

Contactor load
side terminals,
this side for
factory wiring
only.

Active and spare
fuses (see parts list)

Printed circuit board’s
terminal block

Control Enclosure & Field Wiring

External
Bonding