Operating the at10.1 – Exide Technologies Section 94.20 User Manual

Page 44

Advertising
background image

OPERATING THE AT10.1

40

2.4. Performing routine maintenance

WARNING

High voltages appear at several points inside the AT10.1. Use extreme
caution when working inside the unit. Do not attempt to work inside the
AT10.1 unless you are a qualified technician or electrician.

Disconnect and lock out all power from the AT10.1 before starting to
remove or replace any components. Turn the ac power off at the
distribution panel upstream from the charger. Disconnect the battery
from the AT10.1 output terminals TB1(+/-).

2.4.1. Keep it clean

The AT10.1 charger is cooled by natural convection. At least once a year,
vacuum the vents at the top and bottom of the enclosure to ensure that
there is an adequate supply of cooling air. If you have an extremely dusty
environment (especially if airborne dust is conductive), carefully vacuum
out the interior. Be sure to clean surfaces of circuit boards, and around
electrical terminals.

The AT10.1 is rated for operation up to 122° F / 50° C. If your charger is
in a warmer environment, or at an elevation over 3000ft / 914m, contact
your sales representative for operating information.

2.4.2. Check power and signal connections

Check the tightness of all field connections inside the charger, and
connections to the battery. A loose or corroded connection at the battery
terminals can be a fire or explosion hazard, and may cause erroneous
operation of the AT10.1 charger.

2.4.3. Check remote sense wiring (optional)

If you wired the AT10.1 charger for remote sense, check the signal
connections to the battery or load, and check the wiring to be sure the
insulation is in good condition. If there is a failure of the remote sense
signal wiring, the AT10.1 charger displays the error code E 06, and goes
back to local control, sensing the output voltage at the charger output
terminals.