Return Air
Sampling Tube

C08129

Fig. 22 -- Return Air Sampling Tube Location

Completing Installation of Return Air Smoke

Sensor:

SCREWS

EXHAUST
TUBE

FLEXIBLE
EXTENSION
TUBE

SAMPLING

C08126

Fig. 23 -- Return Air Detector Shipping Position

1. Unscrew the two screws holding the Return Air

Sensor detector plate. (See Fig. 23.) Save the screws.

2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing out-

wards and the sampling tube connection is on the bot-

tom. (See Fig. 24.)

4. Screw the sensor and detector plate into its operating

position using screws from Step 1. Make sure the

sampling tube connection is on the bottom and the ex-

haust tube is on the top. (See Fig. 23.)

5. Connect the flexible tube on the sampling inlet to the

sampling tube on the basepan.

6. For units with an economizer, the sampling tube is in-

tegrated into the economizer housing but the connec-

tion of the flexible tubing to the sampling tube is the

same.

C08127

Fig. 24 -- Return Air Sensor Operating Position

FIOP Smoke Detector Wiring and Response

All units: FIOP smoke detector is configured to

automatically shut down all unit operations when smoke

condition is detected. See Fig. 25, Smoke Detector

Wiring.

Highlight A: JMP 3 is factory--cut, transferring unit

control to smoke detector.

Highlight B: Smoke detector NC contact set will open on

smoke alarm condition, de--energizing the ORN

conductor.