Fig. 25 -- Typical Smoke Detector System Wiring

Highlight C: 24--v power signal via ORN lead is removed

at Smoke Detector input on LCTB; all unit operations

cease immediately.

PremierLinkt and RTU--MP Controls: Unit operating

functions (fan, cooling and heating) are terminated as

described above. In addition:

Highlight D: On smoke alarm condition, the smoke

detector NO Alarm contact will close, supplying 24--v

power to GRA conductor.

Highlight E: GRA lead at Smoke Alarm input on LCTB

provides 24--v signal to FIOP DDC control.

PremierLink: This signal is conveyed to PremierLink

FIOP’s TB1 at terminal TB1--6 (BLU lead). This signal

initiates the FSD sequence by the PremierLink control.

FSD status is reported to connected CCN network.

RTU--MP: The 24--v signal is conveyed to RTU--MP’s

J1--10 input terminal. This signal initiates the FSD

sequence by the RTU--MP control. FSD status is reported

to connected BAS network.

Using Remote Logic: Five conductors are provided for

field use (see Highlight F) for additional annunciation

functions.

Additional Application Data — Refer to Catalog No.

HKRNKA--1XA for discussions on additional control

features of these smoke detectors including multiple unit

coordination. (See Fig. 25.)

Sensor and Controller Tests

Sensor Alarm Test
The sensor alarm test checks a sensor’s ability to signal an

alarm state. This test requires that you use a field provided

SD--MAG test magnet.

OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel

and authority concern.
This test places the duct detector into the alarm state.

Unless part of the test, disconnect all auxiliary

equipment from the controller before performing the

test. If the duct detector is connected to a fire alarm

system,

notify

the

proper

authorities

before

performing the test.

CAUTION

!

Sensor Alarm Test Procedure

1. Hold the test magnet where indicated on the side of

the sensor housing for seven seconds.

2. Verify that the sensor’s Alarm LED turns on.
3. Reset the sensor by holding the test magnet against

the sensor housing for two seconds.

4. Verify that the sensor’s Alarm LED turns off.

Controller Alarm Test
The controller alarm test checks the controller’s ability to

initiate and indicate an alarm state.