Beacon Exit Device

Installation and Wiring Instructions

FOR INSTALLATION ASSISTANCE CONTACT SARGENT • 1-800-810-WIRE (9473) • www.sargentlock.com

4. Alarm Mode Operation/Dip Switch Settings

• Two (2) WHITE LEDs flash continuously
• GREEN Laser ON 3 seconds
• ENGLISH message followed by
• GREEN Laser ON 3 seconds
• SPANISH message followed by
• GREEN Laser ON 3 seconds
• FRENCH message

• Two (2) WHITE LEDs flash continuously
• GREEN Laser ON 3 seconds
• ENGLISH message followed by
• GREEN Laser ON 3 seconds
• SPANISH message followed by

• Two (2) WHITE LEDs flash continuously
• GREEN Laser ON 3 seconds
• ENGLISH message only

• Two (2) WHITE LEDs flash continuously
• ENGLISH message followed by
• SPANISH message followed by
• FRENCH message
• (NO Green LASER)
• NO White LEDs
• GREEN Laser ON 3 seconds
• ENGLISH message followed by
• GREEN Laser ON 3 seconds
• SPANISH message followed by
• GREEN Laser ON 3 seconds
• FRENCH message
• NO White LEDs
• ENGLISH message followed by
• SPANISH message followed by
• FRENCH message
• (NO Green LASER)
• Trouble condition #4
• AMBER LED blinks 4 times and repeats

1

2

3

4

5

6

ON

1

2

3

4

5

6

ON

1

2

3

4

5

6

ON

1

2

3

4

5

6

ON

1

2

3

4

5

6

ON

1

2

3

4

5

6

ON

1

2

3

4

5

6

ON

A. Verify settings are correct for your facility’s

requirements.
NOTE: Device is shipped with factory default settings

(all switches ON - see Fig. 10 below).
Visual and audio (voice messages) will repeat sequence

in Alarm Mode.
If dip switch settings need to be changed from the factory

default, set according to chart (Fig. 11).

Door

Surface

ON

OFF

1 2 3 4 5 6

English

Message

1

2

3

4

5

6

ON

Spanish

Message

French

Message

Not Used

Green

Laser

Two White

High-Intensity

LEDs

Alarm Mode Operation

Dip Switch Settings

Factory default for NAC/CC switch is set to

CC (closed contact).
To change Beacon to NAC Alarm Mode:
A. Flip unit; slide insert assembly out 2 inches (Fig. 12).
B. Set the device for NAC by moving the slide switch

to the left, as shown in Figure 12.
C. Once switch is in proper position, slide insert

assembly back into rail assembly.
D. Refer to

Section III NAC wiring examples

for proper wiring of NAC (vs. CC).

5. Alarm Notification Switch Setting (NAC/CC)

Fig. 12

Fig. 10

Fig. 11

Default Settings