Configuration header, Dip switches, Table 9 — potentiometer inputs and ranges – Carrier 50FK User Manual

Page 26: Table 11 — configuration header jumpers

Advertising
background image

Table 9 — Potentiometer Inputs and Ranges

POTENTIOMETER

DESCRIPTION

LOCATION

CONTROL

VALID

RANGE

DEFAULT VALUE

P1

Supply Air

Set Point

Display

Board

45 to 70 F

45 F if -22 F < P1 < 45 F
70 F if P1 > 70 F OR IF P1 < -22 F

P2*

Economizer

Position

Economizer

Motor

0 to 100%

None (0 if P2 is bad)

P3

Reset Limit

Accessory

Board

0 to 80 F

None (limited to 70 F maximum)

P4†

Demand Limit,

Single-Step

Main Control Box

0 to 100%

None

DLCM-P1

Demand Limit,

2-Step

DLCM Board

50 to 100%

None

DLCM-P2

DLCM Board

0 to 49%

None

P5*

Minimum Economizer

Position

Accessory Board

0 to 100%

None

P6

Warm-Up

Set Point

Accessory Board

40 to 80 F

40 F if 0° F < P6 < 40 F OR IF P6 < 95 F
OR IF P6 < 0
80 F if 80 F < P6 < 95 F

P7**

Reset

Temperature

Reset Board

40 to 100 F

None

*Optional factory-installed economizer is required. Potentiometer P2 is not a set point.

†Accessory two-step demand limit module is required (which has 2 potentiometers), or a 5 to 20 k-ohm

field-supplied potentiometer is required for single-step demand limit.

**Accessory temperature reset is required.

NOTE: Potentiometers P1-P6 input data to pin terminal connector J3.
Potentiometer P7 inputs data to pin terminal connector J1.

Configuration Header

— The configuration header

is a series of 8 small wires that are broken (open circuit) or
unbroken (closed circuit) in a pattern to indicate several unique
characteristics of the unit. The configuration header is fac-
tory set and should not be changed; changing the factory set-
ting may cause the unit to malfunction.

Before start-up, visually check the configuration header

against the factory setting for the unit size. See Table 10 for
factory settings. See Table 11 for purpose for each jumper.

Table 10 — Configuration Header and

DIP Switch Factory Settings

JUMPER OR
SWITCH NO.

UNIT SIZES

034-038,

048-088

UNIT SIZE

044

UNIT SIZE

104

Header

Position

Switch

Position

Header

Position

Switch

Position

Header

Position

Switch

Position

1

Off

Off

Off

2

Off

Off

Off

3

On/Off*

On/Off*

On/Off*

4

On/Off*

On/Off*

On/Off*

5

Off

Off

Off

6

Off

On

On

7

On

Off

Off

8

Off

Off

Off

LEGEND

DIP — Dual, In-Line Package

Broken Jumper (open circuit)

Unbroken Jumper (closed circuit)

*Depending on factory-installed options or field-installed accessories.

Table 11 — Configuration Header Jumpers

JUMPER

NUMBER

FUNCTION

FACTORY

SETTING

MEANING

1,2

Unit Type

▫ Ⅲ

VAV Rooftop Unit

3,4,5

Qty Compressors

Ⅲ ▫ ▫

2 Compressors

6

Expansion Valve

TXV

7

Power Frequency

60 Hz

8

Not Used

No Significance

LEGEND

TXV — Thermostatic Expansion Valve
VAV — Variable-Air Volume

Broken Jumper (open circuit)

Unbroken Jumper (closed circuit)

DIP Switches

— The DIP switches configure the unit

for several factory-installed options and field-installed ac-
cessories, plus factory unloaders. The DIP switches are lo-
cated under a plastic enclosure which must be removed for
access. See Fig. 1. The switches can be field adjusted. Switches
must only be adjusted when control power is deenergized.
See Table 12 for DIP switch purposes and Table 10 for fac-
tory settings of the switch positions.

Disconnect control power before changing the settings
of the DIP switches. To disconnect control power, open
the control circuit breaker.