Table 16 — Quick Test, Thermistor and Potentiometer Check

QUICK

TEST

STEP NO.

NORMAL

DISPLAY

DESCRIPTION

THERMISTOR OR

POTENTIOMETER*

1.4.

1

1 — Thermistor OK
0 — Thermistor Faulty

Supply Air
Thermistor (T1)

1.5.

1

1 — Thermistor OK
0 — Thermistor Faulty

Return Air
Thermistor (T2)

1.6.

1

1 — Thermistor OK
0 — Thermistor Faulty

Circuit 1 Condenser Thermistor
(T3)

1.7.

1

1 — Thermistor OK
0 — Thermistor Faulty

Circuit 2 Condenser Thermistor
(T4)

1.8.

1

1 — Thermistor or Potentiometer OK
0 — Thermistor or Potentiometer Faulty or

Option not used

Accessory Space Temperature Thermistor (T10)
or Accessory Reset Potentiometer (P7)

1.9.

1

1 — Potentiometer OK
0 — Potentiometer Faulty

Supply-Air Set Point
Potentiometer (P1)

2.0.

1

1 — Potentiometer OK
0 — Potentiometer Faulty or Option not used

Accessory Reset Limit
Potentiometer (P3)

2.1.

1

1 — Potentiometer OK
0 — Potentiometer Faulty or Option not used

Accessory Demand Limit
Potentiometer (P4)

2.2.

1

1 — Potentiometer OK
0 — Potentiometer Faulty or Option not used

Minimum Position
Economizer
Potentiometer (P5)

2.3.

1

1 — Potentiometer OK
0 — Potentiometer Faulty or Option not used

Warm-Up Set Point
Potentiometer (P6)

*Potentiometer P2 is not listed since it is not part of the quick test. If on unit start-up a Code 83 is displayed, check potentiometer P2.

Table 17 — Quick Test, Output Relay Check

QUICK

TEST

STEP NO.

NORMAL

DISPLAY

DESCRIPTION

RELAY NUMBER

2.4.

1

1 — Open Economizer or Open Relay if no Economizer

K7

2.5.

1

1 — Close Economizer or Close Relay if no Economizer

K8

2.6.

1

1 — Energize Fan Relay and Heat Relay

K9* and K10

2.7.

1

Energize Stage 1 Condenser Fan(s)

K11

2.8.

1

Energize Stage 2 Condenser Fan(s)

K12

2.9.

0 then 1 then 0

Energize Compressor 1†

K1

3.0.

0

Energize Unloader 2; Not Used (044, 104)

K2

3.1.

0

Energize Unloader 1

K3

3.2.

0 then 1 then 0

Energize Compressor 2†

K5

3.3.

0

Not Used

K6

LEGEND

CR — Control Relay

*K9 (fan relay) will remain on for duration of quick test.

†Compressor will be energized for 10 seconds. Zero indicates open CR; 1 indicates closed CR.

33