COMPLETE REPLACEMENT OF VALVE BODY:

1. Make sure when you order complete body replacement assemblies that the new assemblies

are identical to the original. Always reference your check valve’s part number when ordering

replacements.

2. Remove nuts and bolts using the correct size wrench (caution, using incorrect size wrench

may damage the bolts)

3. Carefully remove valve body and O-ring seals from flanges.

4. Install new O-rings and valve body.

NOTE: Insure the arrow indicated on valve body follows gas flow.

5. Install nuts and bolts as shown in (Figure B).

6. Tighten nuts and bolts following the torque chart provided below.

VALVE SIZE

BOLT SIZE

kgf-cm

In-lbs

N-m

½”

5/16-18 x 2-3/4"

90

78

9

¾”

5/16-18 x 2-3/4"

90

78

9

1"

5/16-18 x 3"

90

78

9

1-1/4”

3/8-16 x 3-1/2"

120

104

12

1-1/2”

3/8-16 x 3-3/4"

120

104

12

2"

1/2-13 x 4-1/2"

120

104

12

2-1/2”

1/2-13 x 4-1/2"

120

104

12

3"

1/2-13 x 6"

120

104

12

4”

1/2-13 x 6-1/2"

120

104

12

Tighten Bolts in the numbered sequence listed below

6