Alarm set-point programming – Carlo Gavazzi UDM35/40 & USC User Manual

Page 12

Advertising
background image

UDM 35/40 PANEL METER USER MANUAL


11


Navigating & Programming within the Linearization Menu

As

appears, press

followed by

and

keys to choose to

ignore or enable linearization

. Press

to confirm your choice

and advance to next step. If you chose YES, you will be prompted to

enter the number of Linearization Points,

using the escape

button

to select the position, and the up

/down

buttons to select

the numerical value, from 01-16. Press enter

to confirm and advance.

Next, the correlation between the inputs and outputs must be defined in
the program.

“In.01” will be displayed. Press

to toggle through the positions, and

use the

and

keys to select the value. Press

to confirm and

advance. “Ou.01” will display next. Again, using the escape key

,

toggle to the appropriate position. Use the

and

keys to select the

value. Press enter

to confirm and advance. Repeat this procedure for

each set of Inputs and Outputs, up through a maximum of 16. Press the
enter key

to confirm. Press

to advance to the next program step

sequence.


Alarm Set-point Programming


Up to 4 alarm set-points may be configured. You may configure each set

point using the following parameters, in order, as shown below:

Minimum set-point limit

Maximum set-point limit

Set-point

setting