Pre-Catalyst Configuration Screen

Figure 15


Output Enable:
This button enables or disables the left or right bank PI control
loop. One bank must be enabled for the controller to function.
O

2

Setpoint Req (V): Sets the initial target voltage for the left and right bank

Pre-Cat O

2

sensors. Typically set between 0.700 and 0.900 Volts.

Start Percent (%): Sets the fuel valve opening when the controller is in the START
mode.
Manual Percent (%): Sets the fuel valve opening when the controller is in the
MANUAL mode.
Fault Percent (%): Sets the fuel valve opening when a pre-cat O

2

sensor fault

occurs if the sensor fault select is set to FAULT.