Checking supply air cfm, Electrical data – Champion Manufacturing D1EB036 User Manual

Page 8

Advertising
background image

173858-YIM-A-0306

8

Unitary Products Group

CHECKING SUPPLY AIR CFM

To check the supply air CFM after the initial balancing has
been completed:

1.

Remove the two ¼ inch dot plugs in the duct panel.

2.

Insert at least 8 inches of ¼ inch tubing into each of
these holes for sufficient penetration into the airflow on
both sides of the indoor coil.

3.

Using an inclined manometer, determine the pressure
drop across the evaporator coil.

4.

Knowing the pressure drop across the coil, the actual
CFM through the unit can be determined from Table 5.

After readings have been obtained, remove the tubes and
reinstall the two ¼ inch plugs removed in Step 1.

TABLE 4: ELECTRICAL DATA

SIZE

(TONS)

MODEL

POWER

COMPRESSOR

(EACH)

OD FAN

MOTORS

(EACH)

SUPPLY

BLOWER

MOTOR

MCA

1

(AMPS)

MOCP

2

(AMPS)

MAX. FUSE

3

SIZE

(AMPS)

RLA

LRA

MCC

036

(3.0)

DEB

380/415-3-50

6.7

39.0

9.5

1.0

1.8

11.2

15

15

048

(4.0)

DEB

380/415-3-50

8.7

66.5

12.5

1.0

3.2

15.1

20

20

060

(5.0)

DEB

380/415-3-50

10.4

73.0

13.0

1.0

2.7

15.7

25

25

1.

Minimum Circuit Ampacity.

2.

Maximum Over Current Protection per standard UL 1995.

3.

Fuse or HACR circuit breaker size installed at factory or field installed.

Failure to properly adjust the total system air quan-
tity can result in extensive system damage.