GENERAL

Model D1EB units are factory assembled cooling only air con-
ditioners designed for outdoor installation on a rooftop or a
slab.

The units are completely assembled on rigid, but easily
removable base rails. All piping, refrigerant charge, and elec-
trical wiring is factory installed and tested. The units require
only electric power and duct connections at the point of instal-
lation.

INSPECTION

As soon as a unit is received, it should be inspected for possi-
ble damage during transit. If damage is evident, the extent of
the damage should be noted on the carrier's freight bill. A
separate request for inspection by the carrier's agent should

be made in writing. Refer to Form 50.15-NM for additional
information.

REFERENCE

Additional information on the design, installation, operation
and service of this equipment is available in the following ref-
erence forms:

173858 - General Installation

036-21686-001 - Technical Guide

REPLACEMENT PARTS

Refer to Replacement Parts Manual for complete listing of
replacement parts on this equipment.

INSTALLATION

LIMITATIONS

These units must be installed in accordance with the follow-
ing national and local safety codes.

1.

National Electrical Code ANSI/NFPS No. 70 or Canadian
Electrical Code Part 1, C22.1 (latest editions).

2.

Local plumbing and waste water codes and other appli-
cable local codes.

Refer to Table 1 for unit application data.

If components are to be added to a unit to meet local codes,
they are to be installed at the dealer's and/or the customer's
expense.

Size of unit for proposed installation should be based on heat
loss/heat gain calculations made in accordance with industry
recognized procedures identified by the Air Conditioning
Contractors of America.

LOCATION

Use the following guidelines to select a suitable location for
these units.

1.

Unit is designed for outdoor installation only.

2.

Condenser must have an unlimited supply of air. Where
a choice of location is possible, position unit on either
north or east side of building.

3.

For ground level installation, a level pad or slab should
be used. The thickness and size of the pad or slab used

D

1

E

B

A

PRODUCT NOMENCLATURE

PRODUCT GENERATION

1 = NEW or Current Design

PRODUCT CATEGORY

D = Single Package Air Conditioner

(Air Cooled)

PRODUCT IDENTIFIER

EB

3

0

6

5

0

FACTORY

INSTALLED ELECTRIC HEAT

A = No Electric Heat Installed

VOLTAGE CODE

50 = 380/415-3-50

NOMINAL COOLING

CAPACITY (MBH)

036 = 36,000 BTUH
048 = 48,000 BTUH
060 = 60,000 BTUH

TABLE 1:

UNIT APPLICATION DATA

Wet Bulb Temperature (°C) of Air on
Evaporator Coil, Min. / Max.

14 / 22

Dry Bulb Temperature (°C) of Air on

Condenser Coil, Min.

1

/ Max.

1.

A low ambient accessory is available for operation
down to 0°F.

7 / 49