Frauenfeld, Switzerland

5.1.3.2 Sample teach-in to object

The sensing range is taught into an object (Calibration curve 2).

Figure 3: Teach-in switching range


Fields highlighted in gray are required only for teach-in with 2-point teach-in.
For an inverted switching range (Calibration curve 3):

The command Teach-in Position B must be used instead of Teach-in Position A for 1-point teach-
in.

For 2-point teach-in the distance from the sensor to Teach-in Position A must be greater than the
distance to Teach-in Position B.

Place object at the desired

switching point

Read taught-in position into the

interim register with the command

Teach-in Position A

Align sensor to reference object

(reflector or background)

Read taught-in position into the

interim register with command

Teach-in Position B

Transfer switching points from

the interim register to the working

register and activate them with

the command Transfer

switching points

Save the changes permanently

with the command Save

parameters

The interim registers Teach-in

positions interim can be read

out at any time, and the read-in

values can be checked

After transfer into the working

register, the interim register is

reset to FFFF FFFF hex