background image

Fuse Holder

Busbar

Molded Case Switch

200kA*

UL508 Manual

Motor Star

ter

5kA***

UL508 Switch

5kA***

Driv

es

5kA***

Contactors

5kA***

Receptacle

10kA

GFCI

Receptacle

2kA

10kA

5kA

Default

Value

Your

Value

Glossary of Terms

Industrial Control Panel - An assembly of a

systematic and standard arrangement of two or more

components such as motor controllers, overload relays,

fused disconnect switches, fuses, and circuit breakers

and related control devices such as pushbutton

stations, selector switches, timers, switches, and

control relays with associated wiring, terminal blocks,

pilot lights and similar components.

Interrupting Rating - The highest current at rated

voltage that a device is intended to interrupt under

standard test conditions.

Short-Circuit Current Rating – The prospective

symmetrical fault current at a nominal voltage to which

an apparatus or system is able to be connected without

sustaining damage exceeding the defined acceptance

criteria

Control Circuit – A circuit that carries the electric

signals directing the performance of a controller, and

which does not carry the main power circuit. A control

circuit is, in most cases, limited to 15 amp.

Power Circuit – Conductors and components of

supply, branch, and feeder circuits, supplying main line

power to loads such as heaters, motors, lighting,

receptacles, power transformers, and appliances.