FIND IT – Look for... the Weakest Link

The SCCR marking for the assembly will be based

upon the lowest short-circuit current or withstand rating

of any power circuit component contained within the

assembly — or the “weakest link”. Many components

used in industrial control panels, industrial machinery

and HVAC equipment may be the weakest link,

including:

• motor controllers

• definite purpose contactors

• supplemental protectors

• circuit breakers (with low interrupting ratings)

• power distribution blocks.

FIX IT — How To Get A Higher SCCR So

Equipment Isn’t Limited

By fixing these weakest links, higher SCCRs can be
achieved. In general, there are three options:

1. Use overcurrent protective devices with

higher interrupting ratings

— Overcurrent

protective devices with low interrupting ratings often
become the weakest link and limit the SCCR of the
assembly. The interrupting ratings of the overcurrent
protective devices used directly affects the assembly
rating. The only fix is to use devices with higher
interrupting ratings.

2.

Use current limitation to fix low rated
components

— It only takes one component with a

low SCCR to limit the entire assembly. Many of the
components used in industrial control applications have
low short-circuit current ratings. Fix these low rated
components and the assembly rating by using
current limitation. Since current-limiting fuses reduce high
level short-circuit currents to a minimal level, they allow
the use of these lower rated devices while
providing a higher SCCR.

3.

Buy more expensive components with
higher ratings

— A 65kA circuit breaker will more

than double your cost compared to a 14kA circuit
breaker. The fusible solution provides an interrupting
rating as high as 200kA, at a comparable cost to your
existing design, making it the most economical solution.

FORGET IT — Use Current-Limiting Fuses

Not only can modern current-limiting fusible solutions

fix undesired weak links and obtain a high assembly

short-circuit current rating, they can also provide

enhancements to your design in the areas of flexibility

of installation, increased workplace safety, and reliable

protection through the life of your equipment. These

enhancements take care of the hassle associated with

equipment with limited ratings so you can FORGET IT!

Benefits of Using Cooper Bussmann Current-

Limiting Fuses

Straight Voltage Ratings:

• Straight voltage ratings allow for more installations where

equipment can be installed. Straight voltage rated
equipment can be installed in any type of electrical system.
With a straight voltage rating you can ship it anywhere and
not have to worry.

High Assembly SCCRs:

• High SCCRs allow for more applications where equipment

can be installed. With a high SCCR you can ship it
anywhere and not have to worry.

• A wider range of fault current levels provides assurance that

the equipment will be installed correctly and safely.

• Meets the UL508A and NEC

®

requirements for SCCR

marking.

• Marketing advantage over competitive equipment with a

lower rating.

Increased Flexibility In Panel Use and Installation:

• Valuable time that was spent gathering information for

proper application is drastically reduced with fuses because
modern current-limiting fuses can provide high assembly
SCCRs and straight voltage ratings since they have:

- High Interrupting Ratings of 200,000A or more

- Excellent current limitation to protect low rated

components at high short-circuit current levels

- Straight voltage ratings so they can be installed in any

type of application independent of the grounding scheme
used, unlike devices with a slash voltage rating which are
limited to installation in ONLY a solidly grounded wye
type system

Find It, Fix It, Forget It

Fuse & Motor Starter
Combination

• Fusible disconnect with

Cooper Bussmann LP-CC
fuses marked interrupting
rating 200kA

• Motor starter marked 50kA

when protected by fuses or
circuit breakers

• The SCCR is 50kA

Circuit Breaker &
Motor Starter
Combination

• Three-pole circuit

breaker marked
interrupting rating 14kA

• Motor starter marked

50kA when protected by
fuses or circuit breakers

• The SCCR is 14kA