Cooper Lighting Sure-Lites Lifeway II Series User Manual

Page 13

Advertising
background image

113904 – System Users Manual

12

Table 5.4 Program Functions

Parameter

Format

Factory Default

Date

MM/DD/YY (Month, Date, Year)

Current Date

Time

HH/MM (Hours, Minutes)

Eastern Stand Time

Monthly Test Date

DD (Date)

15

th

of the Month

Monthly Test Time

HH/MM (Hours, Minutes)

5:00

Yearly Test Date

MM (Month)

01

Yearly Test Time

HH/MM (Hours, Minutes)

8:00

Load Reduction

AAAA(Amps)

0.0A

Low VAC Alarm

VVVV(Volts)

1.0V

High VAC Alarm

VVVV(Volts)

999.9V

Ambient Temp Alarm DDD(Degrees Centigrade)

70°C

Near Low Battery

VVVV(Volts)

43VDC

Near Low Battery Voltage is in VVVV (Volts). The last digit entered is after the decimal

place. I.E. (430 + ENTER) will register 43.0VDC.

Load Reduction Fault is in AAAA (Amps). The last digit entered is after the decimal place.

I.E. (480 + ENTER) will register 48.0 Amps. If the output current under battery power is 1
0 percent below this number, the alarm will be set.

Low AC Voltage Alarm is in VVVV (Volts). The last digit entered is after the decimal

place. I.E. (1200 + ENTER) will register 120.0 Volts. If the Input AC Voltage goes below
this number the alarm will be set.

High AC Voltage Alarm is similar to Low AC Voltage Alarm.

Ambient Temperature Alarm is in DDD (Degrees Centigrade). I.E. (75 + ENTER) will

register 75 deg. C. When the ambient temperature internal to the inverter enclosure goes
above the set point the alarm will be set.