113904 – System Users Manual

13

C H A P T E R 6

SPECIFICATIONS

General Specifications

Input

Voltage 120 or 277Vac 1-phase 2-wire +10% -15%. Contact factory for all other voltages.

Input Power Walk-in Limiting inrush current to less than 125%, 10 times for 1 line cycle

Input Frequency 60Hz, +/- 3%, 50Hz Available upon request

Synchronizing Slew Rate 1Hz per second nominal

Protection Input Circuit Breaker

Harmonic Distortion < 10%

Power Factor .5 lag/lead

Output

Voltage 120 or 277Vac 1-phase 2-wire. Contact factory for all other voltages.

Static Voltage Load current change +/-2%, battery discharge +/-12.5%

Dynamic Voltage +/- 2% for +/-25% load step change, +/-3% for a 50% load step change, recovery within 3 cycles

Harmonic Distortion < 3% THD for linear load

Overload Fuse protected

Output Frequency 60Hz +/- .05Hz during emergency mode

Load Power Factor .5 lag to .5 lead

Inverter Overload 125% for 5 minutes

Protection Circuit Breaker

Battery

Type Valve-regulated sealed lead-calcium.

Charger Microprocessor controlled for various battery types and temperature compensating (recharge per UL924 spec)

Protection Automatic low-battery disconnect; automatic restart upon utility return.

Disconnect Circuit Breaker & Fuse

Optional Runtimes Extended runtimes available. Consult factory for additional information.

Environmental

Altitude < 10,000 feet (above sea level) without derating

Operating Temperature 20 to 30 degree Celsius

Storage Temperature -20 to 70 degrees Celsius (electronics only)

Relative Humidity < 95% (non-condensing)

General

Design Stand-By UPS System. PWM inverter type utilizing MOSFET technology with 2mS transfer time.

Generator Input Compatible with generators.

Control Panel Microprocessor controlled 2 x 20-charactor Display with touch pad controls & functions

5 LED indicators & alarm with ring-back feature

Metering Input & Output Voltage, Battery Voltage, Battery & Output Current, Output VA, Temperature, Inverter Wattage

Alarms High/Low Battery Charger Fault, Near Low Battery, Low Battery, Load Reduction Fault, Output Overload,

High/Low AC Input Volts, High Ambient Temperature, Inverter Fault, Output Fault, Optional Circuit Breaker Trip

Communications Optional RS-232 port (DB9)

Manual Maintenance Bypass Optional external without internal distribution breakers.

Alarm Contacts Optional Summary Form "C" Contacts

Warranty 1 year standard warranty includes all parts, labor, & travel expenses within 48 contiguous states. Up to 10 years

prorated warranty on batteries. Extended warranties, preventative maintenance and customized service plans
are available.

Factory Start-up Purchase factory start-up & receive 1 additional year of warranty.

5 Year Service Plan Purchase 5 year service plan & receive free factory start-up.

Physical

Cabinet Freestanding NEMA Type 1

Cooling Forced Air, during emergency mode.

Cable Entry Left-Side

Access Front