Fault finders guide d3 / d5 operators – Centurion CP72SR5 User Manual

Page 33

Advertising
background image

31

PROCEDURE TO PROGRAMME CONTROLLER

BACK TO FACTORY SETTINGS

1. REMOVE POWER (POWER SUPPLY AND BATTERY IF D3 or D5).

2. FIT THE "SET" LINK.

3. CONNECT "PED" AND "FRX" TO "COM".

4. RECONNECT POWER. L1 AND L2 WILL ILLUMINATE.

5. REMOVE THE POWER (BATTERY AND POWER SUPPLY).

6. REMOVE THE "SET" LINK AND DISCONNECT "PED" AND "FRX" FROM "COM".

7. THE CARD IS NOW PROGRAMMED TO DEFAULT SETTINGS AS SHOWN IN

TABLES 2 (see page 28) AND TABLE 3 (see page 30) (GATE END POINTS ARE
NOT AFFECTED).

FAULT FINDERS GUIDE D3 / D5 OPERATORS

REF: CP157

EFFECTIVE: 19/09/2001

SUPERCEDE: 29/11/2000

SOME TYPICAL FAULTS

1. GATE RUNS A SHORT DISTANCE AND STOPS.

1.1 Battery low condition (Status flashing 3 times)

1.1.1 Old battery
1.1.2 Check battery charger

1.1.2.1 Charge voltage (13.8V no battery connected)
1.1.2.2 Charge rate (Check recovery rate of charger)

1.1.3 Check duty cycle of system (battery capacity sufficient)
1.1.4 Check condition of battery leads and connectors.

1.2 Multiple collision condition (Status flashing 4 times)

1.2.1 Adjust collision sensitivity (high to medium or to low)
1.2.2 Check for something physically obstructing the movement of gate

1.2.2.1 Rack pressing down onto pinion
1.2.2.2 Bad rack joints
1.2.2.3 Seized or badly running wheels
1.2.2.4 Top guide rollers restricting the gate
1.2.2.5 Dirt on rail
1.2.2.6 Physical damage to the rail
1.2.2.7 Wheel catching side of pinion
1.2.2.8 Gate hitting endstop

1.2.3 DOSS feedback problem

1.2.3.1 Dirt inside the DOSS
1.2.3.2 Poor connection between the DOSS and the controller (check cable and connector)
1.2.3.3 Doss cable fitted back to front
1.2.3.4 Doss not being driven due to missing coupling or faulty bevel drive.
1.2.3.5 Faulty DOSS controller

1.2.4 Faulty motor circuit

1.2.4.1 Motor fuseholder making intermittent contact.

1.3 Spurious trigger
1.4 Faulty controller

Advertising