Carrier AQUASNAP MPW015-045 User Manual

Aquasnap

Advertising
background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53300053-01

Printed in U.S.A.

Form 30MP-1T

Pg 1

1-10

Replaces: New

Controls, Start-Up, Operation,

Service, and Troubleshooting

SAFETY CONSIDERATIONS

Installing, starting up, and servicing this equipment can be

hazardous due to system pressures, electrical components, and

equipment location (elevated structures, mechanical rooms,

etc.). Only trained, qualified installers and service mechanics

should install, start up, and service this equipment.

When working on this equipment, observe precautions in

the literature, and on tags, stickers, and labels attached to the

equipment, and any other safety precautions that apply. Follow

all safety codes. Wear safety glasses and work gloves. Use

care in handling, rigging, and setting this equipment, and in

handling all electrical components.

WARNING

Electrical shock can cause personal injury and death. Shut

off all power to this equipment during installation. There

may be more than one disconnect switch. Tag all discon-

nect locations to alert others not to restore power until work

is completed.

WARNING

DO NOT VENT refrigerant relief valves within a building.

Outlet from relief valves must be vented outdoors in

accordance with the latest edition of ANSI/ASHRAE

(American National Standards Institute/American Society

of Heating, Refrigerating and Air Conditioning Engineers)

15 (Safety Code for Mechanical Refrigeration). The

accumulation of refrigerant in an enclosed space can

displace oxygen and cause asphyxiation. Provide adequate

ventilation in enclosed or low overhead areas. Inhalation of

high concentrations of vapor is harmful and may cause

heart irregularities, unconsciousness or death. Misuse can

be fatal. Vapor is heavier than air and reduces the amount

of oxygen available for breathing. Product causes eye and

skin irritation. Decomposition products are hazardous.

WARNING

DO NOT attempt to unbraze factory joints when servicing

this equipment. Compressor oil is flammable and there is

no way to detect how much oil may be in any of the

refrigerant lines. Cut lines with a tubing cutter as required

when performing service. Use a pan to catch any oil that

may come out of the lines and as a gage for how much oil

to add to system. DO NOT re-use compressor oil. Damage

to equipment or personal injury may result.

CAUTION

This unit uses a microprocessor-based electronic control

system. Do not use jumpers or other tools to short out

components, or to bypass or otherwise depart from recom-

mended procedures. Any short-to-ground of the control

board or accompanying wiring may destroy the electronic

modules or electrical components.

CAUTION

To prevent potential damage to heat exchanger, always run

fluid through heat exchanger when adding or removing

refrigerant charge. Use appropriate brine solutions in cooler

fluid loop to prevent the freezing of brazed plate heat

exchanger when the equipment is exposed to temperatures

below 32 F (0° C). Proof of flow switch is factory installed

on all models. Do NOT remove power from this chiller dur-

ing winter shutdown periods without taking precaution to

remove all water from heat exchanger and optional

hydronic system. Failure to properly protect the system

from freezing may constitute abuse and may void warranty.

CAUTION

Compressors require specific rotation. Monitor control

alarms during first compressor start up for reverse rotation

protection. Damage to unit may result.

CAUTION

Refrigerant charge must be removed slowly to prevent loss

of compressor oil that could result in compressor failure.

CAUTION

Puron

®

refrigerant (R-410A) systems operate at higher

pressures than standard R-22 systems. Do not use R-22 ser-

vice equipment or components on Puron refrigerant equip-

ment. If service equipment is not rated for Puron

refrigerant, equipment damage or personal injury may

result.

AQUASNAP

®

30MPA,MPW015-045

Liquid Chillers with Scroll Compressors

and ComfortLink™ Controls

Advertising