Carrier AQUASNAP MPW015-045 User Manual

Page 31

Advertising
background image

31

Under normal operation, the chiller will maintain a constant

leaving fluid temperature approximately equal to the chilled

fluid set point. As the cooler load varies, the entering cooler

fluid will change in proportion to the load as shown in Fig. 17.

Usually the chiller size and leaving-fluid temperature set point

are selected based on a full-load condition. At part load, the flu-

id temperature set point may be colder than required. If the

leaving fluid temperature was allowed to increase at part load,

the efficiency of the machine would increase.

Return temperature reset allows for the leaving temperature

set point to be reset upward as a function of the return fluid

temperature or, in effect, the building load.

Demand Limit —

Demand limit is a feature that allows

the unit capacity to be limited during periods of peak energy us-

age. There are 3 types of demand limiting that can be config-

ured. The first type is through 2-stage switch control, which will

reduce the maximum capacity to 2 user-configurable percentag-

es. The second type is by 4 to 20 mA signal input which will re-

duce the maximum capacity linearly between 100% at a 4 mA

input signal (no reduction) down to the user-configurable level

at a 20 mA input signal. The third type uses the CCN Loadshed

module and has the ability to limit the current operating capaci-

ty to maximum and further reduce the capacity if required.
NOTE: The 2-stage switch control and 4 to 20-mA input sig-

nal types of demand limiting require the energy management

module (EMM).

To use demand limit, select the type of demand limiting to

use. Then configure the demand limit set points based on the

type selected.
DEMAND LIMIT (2-Stage Switch Controlled) — To con-

figure demand limit for 2-stage switch control set the Demand

Limit Select (Configuration

RSET

DMDC) to 1. Then

configure the 2 Demand Limit Switch points (Configura-

tion

RSET

DLS1) and (Configuration

RSET



DLS2)

to the desired capacity limit. See Table 27. Capacity steps are

controlled by 2 relay switch inputs field wired to LVT as shown

in Fig. 5.

For demand limit by 2-stage switch control, closing the first

stage demand limit contact will put the unit on the first demand

limit level. The unit will not exceed the percentage of capacity

entered as Demand Limit Switch 1 set point (DLS1). Closing

contacts on the second demand limit switch prevents the unit

from exceeding the capacity entered as Demand Limit Switch

2 set point. The demand limit stage that is set to the lowest de-

mand takes priority if both demand limit inputs are closed. If

the demand limit percentage does not match unit staging, the

unit will limit capacity to the closest capacity stage.

To disable demand limit configure DMDC to 0. See

Table 27.
EXTERNALLY POWERED DEMAND LIMIT (4 to

20 mA Controlled) — To configure demand limit for 4 to 20

mA control set the Demand Limit Select (Configura-

tion

RSET

DMDC) to 2. Then configure the Demand

Limit at 20 mA (Configuration

RSET

DM20) to the

maximum loadshed value desired. Connect the output from an

externally powered 4 to 20 mA signal to terminal block LVT,

terminals 7 and 8 (+,–). Refer to the unit wiring diagram for

these connections to the optional/accessory energy manage-

ment module and terminal block. The control will reduce al-

lowable capacity to this level for the 20 mA signal. See Table

27 and Fig. 18.

LEGEND

LWT — Leaving Water (Fluid) Temperature

Fig. 15 — Outdoor-Air Temperature Reset

LEGEND

LWT — Leaving Water (Fluid) Temperature

Fig. 16 — Space Temperature Reset

CAUTION

Care should be taken when interfacing with other manufac-

turer’s control systems, due to possible power supply

differences, full wave bridge versus half wave rectification.

The two different power supplies cannot be mixed.

ComfortLink™ controls use half wave rectification. A sig-

nal isolation device should be utilized if a full wave bridge

signal generating device is used.

LW

T

LW

T

LEGEND

Fig. 17 — Standard Chilled Fluid

Temperature Control — No Reset

EWT

Entering Water (Fluid) Temperature

LWT

Leaving Water (Fluid) Temperature

Advertising